Electrical Tests - Siemens SIPROTEC 4 7SD80 Manual

Line differential protection
Table of Contents

Advertisement

Technical Data
4.1 General Device Data
Test voltage (with regard to the socket)
(PELV)
Transmission speed
Bridgeable distance
Ethernet optical (EN 100) for DIGSI, IEC61850
Terminal
Transmission speed
Optical wavelength
Bridgeable distance
4.1.5

Electrical Tests

Standards
Standards:
Insulation Tests
Normen:
High voltage test (routine test). All circuits except
power supply, binary inputs, communication inter-
faces and CU protection data interface
High voltage test (routine test). Auxiliary voltage
and binary inputs
High voltage test (routine test): isolated communi-
cation interfaces (A and B)
Voltage test (routine test) CU protection data inter-
face
1)
Impulse voltage test (type test), all processor
circuits against each other and against the
grounding terminal (except communication inter-
face and CU protection data interface) category III
Impulse voltage test (type test), all processor
circuits against the internal electronics (except
communication interface and CU protection data
interface)
Impulse voltage test (type test), all processor
circuits against the CU protection data interface
Voltage test (type test) only CU protection data
interface against all processor circuits
Voltage test (type test) only CU protection data
interface against protective grounding terminal
1)
Protection circuits through surge arresters on the primary side
2)
(type test) not against protective conductor and internal electronic components. Protection circuits through
surge arresters on the primary side
3)
Voltage test without surge arresters (only type test), see also Section 3.1 Mounting and Connections
254
500 V; 50 Hz
100 MBit/s
20 m
Back case bottom, mounting location "B",
Duplex-LC, 100BaseF according to IEEE802.3
100 MBit/s
1300 nm
max. 2 km (1.24 mi)
IEC 60255
IEEE Std C37.90, see individual functions
VDE 0435
for more standards see also individual functions
IEC 60255-27 and IEC 60870-2-1
2.5 kV, 50 Hz
DC 3.5 kV
500 V, 50 Hz
DC 70 V
5 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
6 kV (peak value);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
6 kV (peak value);
2)
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at intervals of 1 s
DC 3.5 kV
2)
1.9 kV, 50 Hz
3)
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018

Advertisement

Table of Contents
loading

Table of Contents