Technical Data
4.8 Inrush Current Restraint Breaker Intertrip and Remote Tripping
4.8
Inrush Current Restraint Breaker Intertrip and Remote Tripping
Phase Comparison Protection
Restraint ratio
2. Harmonische zur Grundschwingung Ι
Max. current for restraint
Crossblock function
Max. action time for crossblock CROSSB 2HM
Restricted Earth Fault Protection
Restraint ratio
2. Inrush stabilization Ι
2fNom
Max. current for restraint
Crossblock function
Max. action time for crossblock CROSSB 2HM
274
/Ι
2fNom
fNom
Ι
Ι
/Ι
fNom
Ι
Ι
0 % to 45 %
= 1 A
1.1 A to 25.0 A
Nom
= 5 A
5.5 A to 125.0 A
Nom
can be switched on/off
0.00 s to 60.00 s
or 0 (crossblock deactivated)
or ∞ (active until dropout)
0 % to 45 %
1.1 A to 25.0 A
= 1 A
Nom
= 5 A
5.5 A to 125.0 A
Nom
zu- und abschaltbar
0.00 s to 60.00 s
or 0 (crossblock deactivated)
or ∞ (active until dropout)
Increments 1 %
Increments 0.1 A
Increments 0.01 s
Increments 1 %
Increments 0.1 A
Increments 0.01 s
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018