Oscillographic Fault Records - Siemens SIPROTEC 4 7SD80 Manual

Line differential protection
Table of Contents

Advertisement

Addr.
Parameter
206
CT SECONDARY
207
SystemStarpoint
220
I4 transformer
221
I4/Iph CT
230
Rated Frequency
240A
TMin TRIP CMD
241A
TMax CLOSE CMD
242
T-CBtest-dead
260
Threshold BI 1
261
Threshold BI 2
262
Threshold BI 3
263
Threshold BI 4
264
Threshold BI 5
265
Threshold BI 6
266
Threshold BI 7

Oscillographic Fault Records

2.1.4
The 7SD80 multifunctional protection with control is equipped with a fault record memory. The instantaneous
values of the measured values
i
, i
, i
, i
, i
und v
A
B
C
E
EE
(voltages in accordance with connection) are sampled at intervals of 1.0 ms (for 50 Hz) and stored in a
revolving buffer (20 samples per cycle). In the event of a fault, the data is stored for a set period of time, but
not for more than 5 seconds. Up to 8 fault events can be recorded in this buffer. The fault record memory is
automatically updated with every new fault so that there is no acknowledgment for previously recorded faults
required. In addition to protection pickup, the recording of the fault event data can also be started via a binary
input or via the serial interface.
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Setting Options
1A
5A
Grounded
Peterson-C.Gnd.
Isolated
Not connected
In prot. line
0.010 .. 5.000
50 Hz
60 Hz
0.02 .. 30.00 sec
0.01 .. 30.00 sec
0.00 .. 30.00 sec
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
Thresh. BI 176V
Thresh. BI 88V
Thresh. BI 19V
, v
, v
, 3Ι0
, 3Ι0
A
B
C
diff
rest
Default Setting
Comments
1A
CT Rated Secondary Current
Grounded
System Starpoint is
In prot. line
I4 current transformer is
1.000
Matching ratio I4/Iph for CT's
50 Hz
Rated Frequency
0.10 sec
Minimum TRIP Command Duration
1.00 sec
Maximum Close Command Dura-
tion
0.10 sec
Dead Time for CB test-autoreclo-
sure
Thresh. BI 176V
Threshold for Binary Input 1
Thresh. BI 176V
Threshold for Binary Input 2
Thresh. BI 176V
Threshold for Binary Input 3
Thresh. BI 176V
Threshold for Binary Input 4
Thresh. BI 176V
Threshold for Binary Input 5
Thresh. BI 176V
Threshold for Binary Input 6
Thresh. BI 176V
Threshold for Binary Input 7
Functions
2.1 General
39

Advertisement

Table of Contents
loading

Table of Contents