Siemens SIPROTEC 4 7SD80 Manual page 110

Line differential protection
Table of Contents

Advertisement

Functions
2.8 Undervoltage and Overvoltage Protection (optional) 27/59
Overvoltage Positive Sequence System V
The device calculates the positive sequence system according to its defining equation
V
=
1
/
·(V
+ a·V
1
3
A
where a = e
j120°
.
The resulting positive sequence voltage is fed to the two threshold elements 59-1-V1 PICKUP (address
3732) and 59-2-V1 PICKUP (address 3734) (see
59-1-V1 DELAY (address 3733) and 59-2-V1 DELAY (address 3735) these elements form a two-element
overvoltage protection for the positive sequence system. Here too, the dropout ratio can be set.
The overvoltage protection for the positive sequence system can also be blocked via a binary input
BLOCK .
[lo-uespg-mitsys-20101108, 1, en_US]
Figure 2-47
Overvoltage Negative Sequence System V
The device calculates the negative sequence system voltages according to its defining equation:
V
=
1
/
·(V
+ a
2
3
A
where a = e
j120°
.
The resulting negative sequence voltage is fed to the two threshold elements 59-1-V2 PICKUP (address
3742) and 59-2-V2 PICKUP (address 3744).
ciated time delays 59-1-V2 DELAY (address 3743) and 59-2-V2 DELAY (address 3745) these elements
form a two-element overvoltage protection for the negative sequence system. Here too, the dropout ratio can
be set.
110
1
+ a
2
·V
)
B
C
Logic diagram of the overvoltage protection for the positive sequence voltage system
2
2
·V
+ a·V
)
B
C
Figure
2-47). Combined with the associated time delays
Figure 2-48
shows the logic diagram. Combined with the asso-
E50417-G1100-C474-A2, Edition 02.2018
>59-V1
SIPROTEC 4, 7SD80, Manual

Advertisement

Table of Contents
loading

Table of Contents