Information List - Siemens SIPROTEC 4 7SD80 Manual

Line differential protection
Table of Contents

Advertisement

Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Addr.
Parameter
1233
CT Err. I1
1234
CT Err. F1
1235
CT Err. I2
1236
CT Err. F2
1237
87NL:Inrush blk
2.2.6.2

Information List

No.
Information
3190
Test 87
3191
Commiss.87
3192
Test 87 remote
3193
Comm. 87 active
3197
>Test 87 ON
3198
>Test 87 OFF
3199
Test 87 ON/off
3200
Test 87 ONoffBI
3260
>Comm. 87 ON
3261
>Comm. 87 OFF
3262
Comm 87 ON/OFF
3263
Comm 87 ONoffBI
32100
>87L block
32102
87L active
32103
87L Fault A
32104
87L Fault B
32105
87L Fault C
32107
87L is blocked
32108
87L is OFF
32109
87L allow A
32110
87L allow B
32111
87L allow C
32112
87 CTRatioAlarm
32113
87L receive blk
32114
87L send blk
32115
87L IDYN> A
32116
87L IDYN> B
32117
87L IDYN> C
32118
87L ISTAT> A
32119
87L ISTAT> B
32120
>87N L block
32121
>87N L active
32122
87(N)L Gen.Flt.
32124
>87N L I> Flt.
64
C
Setting Options
0.003 .. 1.600 A
0.0 .. 5.0 °
0.003 .. 1.600 A
0.0 .. 5.0 °
NO
YES
Type of
Comments
Informa-
tion
IntSP
87 Set test state of 87
IntSP
87 Set Commissioning state of 87
OUT
87 Remote relay in test state
OUT
87 Commissioning state is active
SP
87 >Set test state of 87
SP
87 >Reset test state of 87
IntSP
87 Test state of 87 ON/OFF
IntSP
87 Test state ON/OFF via BI
SP
87 >Commissioning state ON
SP
87 >Commissioning state OFF
IntSP
87 Commissioning state ON/OFF
IntSP
87 Commissioning state ON/OFF via BI
SP
>87L Protection blocking signal
OUT
87L Protection is active
OUT
87L Fault detection A
OUT
87L Fault detection B
OUT
87L Fault detection C
OUT
87L Protection is blocked
OUT
87L Protection is switched off
OUT
87L A released
OUT
87L B released
OUT
87L C released
OUT
87 CT primary ratio is too high
OUT
87L receive blocking
OUT
87L send blocking
OUT
87L IDYN> A
OUT
87L IDYN> B
OUT
87L IDYN> C
OUT
87L ISTAT> A
OUT
87L ISTAT> B
SP
>87N L Protection blocking signal
OUT
>87N L: Protection is active
OUT
87(N)L Fault detection
OUT
>87N L: Fault detection of I-Diff>
Default Setting
Comments
0.050 A
Current I1 for CT Angle
Error
0.0 °
CT Angle Error at I1
1.000 A
Current I2 for CT Angle
Error
0.0 °
CT Angle Error at I2
NO
Inrush blocking
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018