Settings - Siemens SIPROTEC 7ST6 Manual

Numerical overhead contact line protection for ac traction power supply
Table of Contents

Advertisement

2.1.1.3

Settings

Addr.
Parameter
103
Grp Chge OPTION
104
OSC. FAULT REC.
113
DISTANCE CURVE
122
InrushRestraint
124
FCT HS O/C
126
Back-Up O/C
127
FCT Emerg. O/C
133
Auto Reclose
135
Synchro-Check
137
O/U VOLTAGE
138
Fault Locator
139
BREAKER FAILURE
140
Trip Cir. Sup.
141
FCT It-Calc.
142
Therm.Overload
143
Temp.Sens
144
FCT DEFROSTING
7ST6 Manual
E50417-G1176-C251-A3
Setting Options
Disabled
Enabled
Disabled
Enabled
Quadrilateral
Combined
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Start by Aux
Start by TRIP
Disabled
Enabled
Disabled
-30 to +55 °C
-55 to +55 °C
Disabled
Enabled
Default Setting
Enabled
Setting Group Change Option
Enabled
Oscillographic Fault Records
Combined
Distance Curve
Enabled
2nd Harmonic Inrush Restraint
Enabled
Instantan. High-Speed O/C Pro-
tection
Enabled
Backup overcurrent
Enabled
Emergency Overcurrent Protec-
tion
Enabled
Auto-Reclose Function
Enabled
Synchronism and Voltage Check
Enabled
Under / Overvoltage Protection
Enabled
Fault Locator
Enabled
Breaker Failure Protection
Disabled
Trip Circuit Supervision
Start by TRIP
It Function (ampere-seconds)
Disabled
Thermal Overload Protection
Disabled
Ambient Temperature Sensing
Disabled
Defrosting Protection Function
2.1 General