11.7 End-Fault Protection

11.7
End-Fault Protection
Setting Values
Phase-current threshold
values
Delay T, CB open
Tripping delay
Minimum operate time
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer
Instrument current transformer
Frequency Operating Range
0.9 ≤ f/f
≤ 1.1
rated
10 Hz ≤ f < 0.9 f
1.1 f
< f ≤ 80 Hz
rated
f < 10 Hz
f > 80 Hz
Tolerances
Threshold values, dropout thresholds
Times
570
For I
= 1 A
rated
For I
= 5 A
rated
rated
0.03 A to 35.00 A
0.15 A to 175.00 A
0.00 s to 15.00 s
0.00 s to 60.00 s
0.00 s to 60.00 s
15 mA sec. (I
= 1 A) or
rated
75 mA sec. (I
= 5 A)
rated
0.5 mA sec. (I
= 1 A) or
rated
2.5 mA sec. (I
= 5 A)
rated
According to specified tolerances
Slightly expanded tolerances
Active
2 % of the setting value or 1 % of the rated current
1 % of the setting value or 10 ms
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
Increments 0.01 A
Increments of 0.01 s
Increments of 0.01 s
Increments of 0.01 s