Setting the PROFIBUS DP address via DIP switches
The PROFIBUS DP address can be set via DIP switch, as shown in the table below.
Table 3- 16
DIP switch
Add to address
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
3.14

Connecting the PROFINET interface

Industrial Ethernet Cables and cable length
Listed in the table below are the recommended Ethernet cables.
Table 3- 17
Cable type
Industrial Ethernet FC TP Standard Cable GP 2 x 2
Industrial Ethernet FC TP Flexible Cable GP 2 x 2
Industrial Ethernet FC Trailing Cable GP 2 x 2
Industrial Ethernet FC Trailing Cable 2 x 2
Industrial Ethernet FC Marine Cable 2 x 2
Cable screening
The screen of the PROFINET cable must be connected with the protective earth. The solid
copper core must not be scored when the insulation is removed from the core ends.
SINAMICS G120D converter
Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
Example address for the PROFIBUS DP interface
Recommended PROFINET cables
3.14 Connecting the PROFINET interface
1
2
3
4
1
2
4
8
Max. length be-
tween devices
100 m (328 ft)
85 m (278 ft)
85 m (278 ft)
85 m (278 ft)
85 m (278 ft)
Installation
5
6
7
16
32
64
Article Number
6XV1840-2AH10
6XV1870–2B
6XV1870–2D
6XV1840–3AH10
6XV1840–4AH10