Siemens SINAMICS G120D Getting Started page 76

Control units cu240d-2 and cu250d-2 with encoder evaluation
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

Troubleshooting and further information
5.1 List of alarms and faults
Number
Cause
A07584
Position setting value activated
A07585
A07587
Position actual value processing
A07588
does not have a valid encoder
A07593
Value range for position actual
A07594
value exceeded
A07596
Reference function interrupted
A07597
F07599
Adjustment not possible
F07600
F07801
Motor overcurrent
A07805
Drive: Power unit overload I2t
F07806
Regenerative power limit exceeded Increase deceleration ramp.
F07807
Short circuit detected
A07850
External alarm 1 ... 3
A07851
A07852
76
Remedy
The alarm automatically disappears with BI: p2514 = 0 signal.
An encoder data set has been assigned, however, the encoder data set
does not contain any encoder data (p0400 = 0) or invalid data (e.g. p0408
= 0). Remedy: Check the drive data sets and encoder data sets.
The value range (-2147483648 ... 2147483647) for representing the posi-
tion actual value was exceeded. Remedy: Reduce the traversing range or
position resolution. If necessary reduce the traversing range or position
resolution.
An activated reference function (reference mark search or measuring
probe evaluation) was interrupted. Possible causes:
Encoder fault
Reference mark search and measuring probe evaluation simultane-
ously activated (BI: p2508 and BI: p2509 = 1 signal).
Activated reference function (reference mark search or measuring
probe evaluation) was de-activated (BI: p2508 and BI: p2509 = 0 sig-
nal).
The maximum encoder value times the factor to convert the absolute
position (r0483 and/or r2723) from increments to length units (LU) has
exceeded the value range (-2147483648 ... 2147483647) for representing
the position actual value.
Check current limits (p0640).
Vector control: Check current controller (p1715, p1717).
U/f control: Check the current limiting controller (p1340 ... p1346).
Increase acceleration ramp (p1120) or reduce load.
Check motor and motor cables for short circuit and ground fault.
Check motor for star-delta connection and rating plate parameterization.
Check power unit / motor combination.
Select flying restart function (p1200) if switched to rotating motor.
Reduce the continuous load.
Adapt the load cycle.
Check the assignment of rated currents of the motor and power unit.
Reduce driving load.
Use power unit with higher energy recovery capability.
For vector control, the regenerative power limit in p1531 can be reduced
until the fault is no longer activated.
Check the converter connection on the motor side for any phase-
phase short-circuit.
Rule out that line and motor cables have been interchanged.
The signal for "external alarm 1" has been triggered.
Parameters p2112, p2116 and p2117 determine the signal sources for
the external alarm 1... 3.
Remedy: Rectify the cause of these alarms.
Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA