Troubleshooting and further information
5.1 List of alarms and faults
Number
Cause
A31418
Speed difference per sampling rate
exceeded
F31905
Parameterizing error
A31915
Configuration error
F32110
Serial communications error
F32111
Absolute encoder internal error
F32112
A32410
Serial communication
A32411
Absolute encoder outputs alarms
A32412
Error bit set in the serial protocol
A32442
Battery voltage pre-alarm
F32905
Parameterizing error
A32915
Configuration error
For further information, please refer to the List Manual.
80
Remedy
p0492 over several sampling cycles.
Check tachometer feeder cable for interruptions.
Check the grounding of the tachometer shielding.
Increase the maximum speed difference per sampling cycle (p0492).
Check whether the connected encoder type matches the encoder that
has been parameterized.
When the fine resolution Gx_XIST2 is configured, the encoder identifies a
maximum possible absolute position actual value (r0483) that can no
longer be represented within 32 bits. Remedy: Check the encoder data.
The transfer of the serial communication protocol between the encoder
and converter is faulty. Remedy: Check the hardware and the associated
settings in the converter.
Check the power supply of the encoder.
Replace the encoder.
Check that the encoder cables are routed in compliance with EMC.
Check the cable connections.
Replace the encoder.
Replace the encoder.
Carry out a power on reset (power off/on) for all components.
Check that the encoder cables are routed in compliance with EMC.
Check the plug connections.
Replace the encoder
Replace the battery in the encoder.
Check whether the connected encoder type matches the encoder that
has been parameterized.
Correct the parameter specified by the fault value (r0949) and p0187.
When the fine resolution Gx_XIST2 is configured, the encoder identifies a
maximum possible absolute position actual value (r0483) that can no
longer be represented within 32 bits. Remedy: Check the encoder data.
Manuals for the converter (Page 83)