Troubleshooting and further information
5.1 List of alarms and faults
Number
Cause
A07469
Traversing block target position <
software limit switch minus
A07470
Traversing block target position >
software limit switch plus
A07471
Traversing block target position
outside the modulo range
A07472
Traversing block
ABS_POS/ABS_NEG not possible
A07473
Beginning of traversing range
reached
A07474
End of traversing range reached
F07475
Target position < start of traversing
range
F07476
Target position > end of traversing
range
A07477
Target position < software limit
switch minus
A07478
Target position > software limit
switch plus
A07479
Software limit switch, minus actu-
ated
A07480
Software limit switch, plus actuated
F07481
Axis position < software limit switch
minus
F07482
Axis position > software limit switch
plus
A07483
Travel to fixed stop, clamping
torque not reached
F07484
Fixed stop outside the monitoring
window
F07485
Fixed stop is not reached
A07486
Intermediate stop missing
A07487
Reject traversing task missing
74
Remedy
Correct the traversing block.
Change the software limit switch minus (CI: p2578, p2580).
Change the software limit switch plus (CI: p2579, p2581).
Correct the target position in the traversing block.
Change the modulo range (p2576).
Correct the traversing block.
Move away in the positive direction.
Move away in the negative direction.
Correct the target position.
Correct the target position.
Change the software limit switch minus (CI: p2578, p2580).
Change the software limit switch plus (CI: p2579, p2581).
Correct the target position.
Change the software limit switch minus (CI: p2578, p2580).
Change the software limit switch plus (CI: p2579, p2581).
Correct the target position.
Change the software limit switch minus (CI: p2578, p2580).
Change the software limit switch plus (CI: p2579, p2581).
Check the maximum torque-generating current (r1533).
Check the torque limits (p1520, p1521).
Check the power limits (p1530, p1531).
In the "Fixed stop reached" state, the axis has moved outside the defined
monitoring window (p2635). Remedy:
Check the monitoring window (p2635).
Check the mechanical system.
In a traversing block with the FIXED STOP task the end position was
reached without detecting a fixed stop. Remedy:
Check the traversing block and locate the target position further into
the workpiece.
Check the "fixed stop reached" control signal (p2637).
Reduce the maximum following error window to detect the fixed stop
(p2634).
Connect a "1" signal at the binector input "no intermediate
stop/intermediate stop" (BI: p2640) and re-start motion.
Connect a "1" signal at the binector input "do not reject traversing
task/reject traversing task" (BI: p2641) and re-start motion.