Commissioning

4.1

Default settings for the SINAMICS G120D

Factory default settings
The inverter system is shipped from the factory as a Control Unit and a Power Module.
Without any parameterization or after a factory reset, the inverter can be operated without
additional parameterization if the inverter default settings (which depend on the inverter type
and size) match the following data of a 4-pole motor:
Default line supply frequency
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
(A Siemens standard motor is recommended.)
Further, the following conditions must be fulfilled:
Control (ON/OFF command) using digital inputs
Asyncronous motor
Self-cooled motor
Motor overload factor
Min. frequency
Max. frequency
Ramp-up time
Ramp-down time
Linear V/f characteristic
The Control Unit is intended to be control and operate the inverter utilizing the PROFIBUS or
PROFINET interface. The PROFIBUS or PROFINET interface may be used to further
configure and control the inverter as required.
SINAMICS G120D converter
Getting Started, 07/2016, FW V4.7 SP6, A5E38556189B AA
50 Hz
P0304
P0305
P0307
P0310
P0311
See pre-assigned inputs below.
P0300 = 1
P0335 = 0
P0640 = 150 %
P1080 = 0 Hz
P1082 = 50 Hz
P1120 = 10 s
P1121 = 10 s
P1300 = 0
4
61