A. CT Settings window is reached when CT Settings button under the Settings tab is clicked.
B. Save to Buffer button sends the parameter changes to the DigiConnect buffer. When changes are to be
applied to CPM 310 G unit, Save to Device button must be utilized, which is located under the Buffer tab.
1. CT Settings window embeds the settings options for primary and secondary nominal current for phases
and earth. It must be noted that, with the selection of earth secondary nominal current, type of earth
protection and set ranges are also determined. See the dedicated subsection Current Transformer Settings
Menu within the Relay Menus Manual section of this book for detailed information. □