5. Thermal protection of the power transformer, and phase and earth protections are to be done.
Below calculations and settings are done for this purpose.
Making of Iθ> Thermal Overload Protection Settings
It is assumed that the thermal constant for the power transformer is Te = 20 minutes
according to the information supplied by the manufacturer. Take trip threshold translation
constant k as 1.10, thermal overload trip heating as %ΘTrip = %100 and thermal
overload alarm heating as %ΘAlarm = %80.
Power transformer nominal current is:
Power transformer nominal current / Protection CT primary nominal current ratio:
Make the setting below so as to activate thermal overload protection at 1.00 I
Making of I> Phase Overcurrent Protection Settings
a. Around 1.00 I
suitable according to the PT ratings. Threshold set current in terms of I
b. According to the calculation above, do the following settings: ↺
Notes:
If there are loads of high inrush pick-up current, fine adjustment of the TMS parameter
might be needed.
If the Thermal Overload Protection is not applied / made passive, set the I> (Phase
Overcurrent Protection Threshold) as 1.0 I
��
������
��
=
������
√ 3 × ��
41.84 ��
��
=
rTR
60 ��
Main Screen » Set » I
, the PT is protected from overloads. Setting I> threshold at 1.3 I
rTR
�� > = 1.3 × ��
Main Screen » Set » I>
2500 ���� ∙ ��
=
≅ 41.84 ��
√ 3 × 34.5 ����
��
≅ 0.70 ��
��
>
Θ
≅ 0.91 ��
������
��
(0.70 I
) instead of 1.3 I
rTR
n
- 45 -
:
rTR
is
rTR
of CT:
n
(0.91 I
).
rTR
n