Auxiliary Timer Settings Menu

DEMA CPM 310 G Overcurrent Protection Relays are
equipped with 2 independent auxiliary timers. These
timers are set to trip the circuit breaker by default, but
can be utilized for wide range of applications.
Auxiliary timers can be triggered via inputs that are
Start tAux1
Start tAux2
programmed as
or
, and can
tAux1
tAux2
trigger outputs programmed as
or
. Note
that the auxiliary timers can be triggered only
externally via dedicated inputs; e.g. by a button that
energizes an input, to which
StartAux1
function is
assigned; or, by a programmable output relay.
The setting range for auxiliary timers is (0.0 - 600.0) s.
Main Screen » Menu »
Automatic Control Settings »
Auxiliary Timer Settings
- 113 -