DEMA CPM 310 G User Manual page 39

Digital overcurrent protection relay
Table of Contents

Advertisement

Terminal numbers and descriptions are given on the table below.
CAUTION!
The "Notes" columns on the table suggests a sample application and is not normative. "DC(+)" notes,
e.g., are given assuming that the circuit breaker, the power transformer and auxiliary devices are
cabled in the way that their common terminals are supplied with DC(-). If an application does not
correspond to the case here assumed, do not take the note columns into consideration and create the
actual cabling project required to provide the healthy operation of the system. ↺
Terminal No. Terminal Description
Inputs
1
Programmable Input 1
2
Programmable Input 1, common terminal.DC (+)
3
Programmable Input 2
4
Programmable Input 2, common terminal.DC (+)
5
Programmable Input 3
6
Programmable Input 3, common terminal.DC (+)
7
Programmable Input 4
8
Programmable Input 4, common terminal.DC (+)
9
Programmable Input 5
10
Programmable Input 5, common terminal.DC (+)
11
Programmable Input 6
12
Programmable Input 6, common terminal.DC (+)
13
Programmable Input 7
14
Programmable Input 7, common terminal.DC (+)
15
Not used.
RS 485
16
RS 485, 0VISO
17
RS 485, Termination Resistance.
18
RS 485, A terminal.
19
RS 485, B terminal.
20
Not used.
Auxiliary Supply and Earthing
21
Auxiliary Supply Terminal
22
Auxiliary Supply Terminal
23
Internal Circuit Earthing Terminal
24
Not used.
Secondary Current Terminals
25
Current Input Terminal for Phase R
26
Terminal for Current Bridge
27
Current Input Terminal for Phase S
28
Terminal for Current Bridge
29
Current Input Terminal for Phase T
30
Terminal for Current Bridge
31
Current Output Terminal for Neutral Point (1/5)A
32
Terminal for Current Bridge
33
Not used.
Outputs
34
Trip signal common terminal
35
Trip signal N/C terminal
36
Trip signal N/O terminal
37
Watchdog common terminal
38
Watchdog N/C terminal
39
Watchdog N/O terminal
40
Programmable Output 1 Common Terminal DC (+)
41
Programmable Output 1 N/C Terminal
42
Programmable Output 1 N/O Terminal
43
Programmable Output 2 Common Terminal DC (+)
44
Programmable Output 2 N/C Terminal
45
Programmable Output 2 N/O Terminal
46
Programmable Output 3 Common Terminal DC (+)
47
Programmable Output 3 N/O Terminal
48
Programmable Output 4 Common Terminal DC (+)
49
Programmable Output 4 N/O Terminal
50
Programmable Output 5 Common Terminal DC (+)
51
Programmable Output 5 N/O Terminal
52
Programmable Output 6 Common Terminal DC (+)
53
Programmable Output 6 N/O Terminal
54
Not used.
55
Not used.
56
Not used.
57
Not used.
58
Not used.
CPM 310 G Terminal Explanations
Notes
-
-
-
-
-
-
-
-
Reference voltage.
-
-
-
-
DC (-) or AC neutral.
DC (+) or AC phase.
-
-
(1/5)A
-
(1/5)A
-
(1/5)A
-
-
-
DC (+)
DC (+) out.
DC (+) out.
DC (+) or AC phase.
Alarm / Signal output.
Alarm / Signal output.
DC (+) out.
DC (+) out.
DC (+) out.
DC (+) out.
DC (+) out.
DC (+) out.
DC (+) out.
DC (+) out.