IEC Thermal Overload Protection Curve

IEC Thermal Overload Protection formula and sample curves according to this formula are given below.
Formula characteristic is determined by the T
parameters are considered, it is calculated that CPM 310 G relay can run 1,540,000 unique IEC Thermal
Overload Protection curves; for its impossible to demonstrate all of the curves on a chart, sample curves are
given on the below chart to express an overview of the characteristic. □
t
Trip time delay (minute).
T
Thermal Constant (minute); setting range: (1-200) m, in 1m steps.
e
k
Trip Threshold Translation Constant (-); setting range: (1.00-1.50), in 0.01 steps.
I
RMS value of load current (A).
I
Set current (A); setting range: (0.10-3.20) In, in 0.01I
θ
Overload Pre-heating (%); setting range: (50-200) %, in 1% steps.
p
Overload Trip Threshold (%); setting range: (50-200) %, in 1% steps. □
trip
, k, I
, %θ
and %θ
e
θ
p
trip
2
��
(
)
− %Θ
�� × ��
log
Θ
�� = ��
×
��
e
2
��
(
)
− %Θ
[
�� × ��
Θ
steps.
n
- 25 -
parameters. When setting ranges for these
��
��������
]