Trip Settings Menu

Trip Settings Menu
is a control menu where certain
protection and auxiliary timer functions, which are
normally expected to give tripping signal to the circuit
breaker, are set to trip the CB or not.
Active
Setting trip functions to
(let CPM 310 G to trip
Passive
the CB by that function) or
(prevent CPM 310 G
to trip the CB by that function) may be needed in many
types of applications, e.g.,
• I>>> and I
>>> functions can be set active to
e
monitor the pick-up current, while their tripping
settings are set to Passive, therefor are not let to trip
the CB. By utilizing this method, it is possible to acquire
information without tripping the CB, whether a device's
Main Screen » Menu »
(e.g. an asynchronous motor) pick-up current exceeds
Automatic Control Settings »
a specified limit,
Trip Settings
• A function test of CPM 310 G may be needed to be
conducted online – in this case, setting all parameters
in Trip Settings Menu will do the trick.
As seen on the pictures to the left, all functions that
normally lead to the tripping of the CB can be
controlled from the menu. The sample picture shows
the default values; with which all protection and
auxiliary timer functions will trip the CB when triggered.
WARNING!
Trip settings are to be modified only by the authorized
personnel; since changes on those settings can prevent
the relay to interrupt faults!
If the settings on the Trip Settings Menu are done
inappropriately, the resulting behavior of the relay may
cause system stresses, failure of fault interrupting,
facility damages, selectivity failures and supply
discontinuity! □
- 106 -