PC mode
4.2 Parameters/address space
4.2.3

Address space

The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image output/input.
Configuration options of the DQ 4×24..230VAC/2A HF in PC mode
You can configure the module with STEP 7 (TIA Portal) or with a GSD file. When you
configure the module by means of the GSD file, the configuration is available under different
short designations/module names. The following configurations are possible:
Table 4- 2
Configuration options with GSD file
Configuration
1 x 4-channel without value
status
1 x 4-channel with value status
Note
The following functions are only fully available when the submodule X.1 is configured and
the IO controller to which submodule X.1 is assigned has established a connection to the IO
device.
• Firmware update
• I&M identification data
• PROFIenergy
Value status (quality information, QI)
The value status is always activated for the following module names:
● DQ 4×24..230VAC/2A HF PC V1.0, QI
An additional bit is assigned to each channel for the value status. The bit for the value status
indicates if the output value specified by the user program is actually pending at the module
terminal (0 = value is incorrect).
38
Short designation/module
name in the GSD file
DQ 4×24..230VAC/2A HF
PC V1.0
DQ 4×24..230VAC/2A HF
PC V1.0, QI
DQ 4x24..230VAC/2A HF digital output module (6ES7132-6FD00-0CU0)
Configuration software, e.g. STEP 7 (TIA Portal)
Integrated in the
hardware catalog
PROFINET IO
STEP 7, V14 or
higher
X
X
GSD file
GSD file
PROFIBUS DP
X
X
X
---