DQ mode
3.3 Interrupts/diagnostics alarms
3.3.3
Diagnostics alarms
Diagnostics alarms
A diagnostics alarm is generated and the DIAG-LED flashes on the module for each
diagnostics event. You can read out the diagnostics alarms, for example, in the diagnostics
buffer of the CPU. You can evaluate the error codes with the user program.
In DQ mode, the module outputs the following diagnostic alarms:
Table 3- 6
Diagnostics alarms, their meaning and corrective measures
Diagnostics alarms
Overtemperature
Wire break
Parameter assignment
error
Supply voltage missing
Channel/component
temporarily unavailable
28
Error
Meaning
code
5
Possible causes:
H
Short-circuit or overload at the digital
•
outputs
Ambient temperature outside the spec-
•
ification
6
Actuator circuit impedance too high
H
Wirebreak between the module and ac-
tuator
Channel not connected (open)
10
The module cannot evaluate parame-
•
H
ters for the channel.
Incorrect parameter assignment.
•
11
No or insufficient supply voltage L
H
1F
Firmware update is currently in progress
H
or has been canceled. The module does
not output any process or substitute val-
ues in this state.
Solution
•
•
•
Use a different actuator type or modify
the wiring, for example, use cables with
larger cross-section
Connect the cable
Disable diagnostics
Correct the parameter assignment
•
•
•
•
DQ 4x24..230VAC/2A HF digital output module (6ES7132-6FD00-0CU0)
Correct the process wiring
Improve cooling
Check controlled loads
Check supply voltage L at the Ba-
seUnit
Check BaseUnit type
Wait for firmware update.
Restart the firmware update.
Manual, 02/2018, A5E42404845-AA