Digital output module dq 4x24..230vac/2a hf 6es7132-6fd00-0cu0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Reaction to CPU STOP
Determines the behavior of the module in the event of a CPU STOP.
Channel startup delay
Specifies the duration of the startup delay of a channel.
You can set startup delays with values ranging from 100 ms to 10 s. This means the
channels cannot be controlled before the set startup delay has expired.
Configure different startup delays for each channel to decouple the starting currents and thus
reduce the network load.
Startup delays are also in effect when the module is to output substitute values. The startup
delay starts after the module was started and when the load voltage returns.
This means that depending on your process, the initial switch on of lamps is always delayed
by the configured time.
DQ 4x24..230VAC/2A HF digital output module (6ES7132-6FD00-0CU0)
Manual, 02/2018, A5E42404845-AA