PC mode

4.1

Wiring

4.1.1

Wiring and block diagram

This section includes the block diagram of the DQ 4x24..230VAC/2A HF module with the
terminal assignments for a 1-wire and 2-wire connection.
You can use the different connection options for all channels and combine them at random.
You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system
(https://support.industry.siemens.com/cs/ww/en/view/58649293) system manual.
Dangerous voltage. Risk of death or serious injury.
You must always disconnect the system and module from the power supply before
commencing work.
Note
Limiting overvoltage
You must ensure overvoltage of the encoder supply is limited to 1 kV.
Note
Power limitation
To limit power, each input voltage must have a fuse with a maximum rating of 10 A tripping
current. The fuse must be a quick-acting microfuse.
Note
Three-phase loads
Do not connect any three-phase loads to the module. The digital output is not suitable for
three-phase loads.
DQ 4x24..230VAC/2A HF digital output module (6ES7132-6FD00-0CU0)