Installation
f 0
f 0
i F 40 °C
f
F 4 kHz (P11.9)
PWM
Figure 19: Free space at the sides
Up to an ambient temperature of +40 °C, a set-up height of up to
1000 m and a pulse frequency of up to 4 kHz, the frequency
TM
inverters of the M-Max
series do not require any space at the
sides.
Higher ambient temperatures (up to a maximum of +50 °C), pulse
frequencies f
(up to maximum 16 kHz) and set-up heights (up
PWM
to 2000 m) require space on the sides of at least 20 mm.
h
The pulse frequency (f
parameter P11.9.
h
Devices with strong magnetic fields (e.g. inductors or
transformers) should not be installed in the immediate
vicinity of the M-Max
32
f 20
f 0.498"
i > 40 °C (max. 50 °C)
f
> 4 kHz (P11.9)
PWM
) can be adjusted with
PWM
TM
device.

Fixing

TM
You can mount an M-Max
frequency inverter on screw mounts
or on a mounting rail.
h
Install the frequency inverter only on a nonflammable
mounting base (e.g., on a metal plate).
h
Dimensions and weights of the frequency inverter
TM
M-Max
are located in the appendix.
Fastening with screws
The number and arrangement of required bore holes (mounting
dimensions a1 and b1 in figure 20) are also imprinted in the base
TM
plate of the M-Max
device.
7 mm
(0.275")
Figure 20: Mounting dimensions
Install the screws in the specified positions first. Then set the
frequency inverter on the prepared wall-mount and tighten all
screws. The permitted maximum tightening torque for the
fastening screws is 1.3 Nm.
= M4
1.3 Nm (11.5 lb-in)
Figure 21:
Configuration for mounting with screws
04/10 MN04020001Z-EN
a1
= M5
1.3 Nm (11.5 lb-in)

Hide quick links: