Proof Test Procedure Hic2871 - Pepperl+Fuchs SIL KFD0-SD2-*. Series Safety Manual

Solenoid driver
Table of Contents

Advertisement

SAFETY MANUAL SIL K*D0-SD*-(EX)*.****(.SP), HIC2871
Proof Test
4.1.3

Proof Test Procedure HiC2871

Connect the module specific load resistor between the terminals 1+ and 4-.
Connect the power supply set at nominal 20 V DC between terminals 11+
and 14-.
Measure the output voltage via multimeter. Compare the resulting value to
the nominal value specified in the table below.
Short circuit the load resistor and measure the short circuit current via
multimeter. Compare the resulting value to the nominal value specified in the
table below.
Module
HiC2871
Table 4.3
SC
Figure 4.3
Tip
Normally the easiest way to test H-System modules is by using a stand-alone
HiCTB08-UNI-SC-SC Termination Board. The tester then has no need to
disconnect wires in the existing application, so subsequent miswiring of the
module is prevented.
Multimeter
Multimeter
(mA)
(V)
SL2
1+
R
load
4-
Zone 0, 1, 2
Div. 1, 2
Proof test set-up for HiC2871
Output resistor
Output voltage
(Ω)
(V)
270
> 12
Termination Board
HiC2871
SL1
11+
14-
Short circuit
current (mA)
45 < I
< 55
sc
V
Zone 2
Div. 2
15