Proof Test Procedure Kcd0-Sd-(Ex)1.****(.Sp) - Pepperl+Fuchs SIL KFD0-SD2-*. Series Safety Manual

Solenoid driver
Table of Contents

Advertisement

SAFETY MANUAL SIL K*D0-SD*-(EX)*.****(.SP), HIC2871
Proof Test
4.1.2

Proof Test Procedure KCD0-SD-(Ex)1.****(.SP)

Connect the module specific load resistor between the terminals 1+ and 2-.
Connect the power supply set at nominal 20 V DC between terminals 5+
and 6-.
Measure the output voltage via multimeter. Compare the resulting value to the
nominal value specified in the table below.
Short circuit the load resistor and measure the short circuit current via
multimeter. Compare the resulting value to the nominal value specified in the
table below.
Module
KCD0-SD-(Ex)1.1245(.SP)
Table 4.2
SC
Figure 4.2
Usage in Zone 0, 1, 2/Div. 1, 2 only for KCD0-SD-Ex1.****(.SP).
14
Multimeter
Multimeter
(mA)
(V)
1+
R
load
2-
Zone 0, 1, 2
Div. 1, 2
Proof test set-up for KCD0-SD-(Ex)1.****(.SP)
Output resistor
Output voltage
(Ω)
(V)
270
> 12
KCD0-SD-Ex1.*
5+
6-
Short circuit
current (mA)
45 < I
< 55
sc
V
Zone 2
Div. 2

Hide quick links: