SAFETY MANUAL SIL K*D0-SD*-(EX)*.****(.SP), HIC2871
Planning
2.2

Assumptions

The following assumptions have been made during the FMEDA analysis:
Failure rate based on the Siemens SN29500 data base.
The stress levels are average for an industrial environment and can be
compared to the Ground Fixed Classification of MIL-HNBK-217F.
Alternatively, the assumed environment is similar to:
• IEC 60654-1 Class C (sheltered location) with temperature limits within
It was assumed that the appearance of a safe error (e. g. output in safe state)
would be repaired within 8 hours (e. g. remove sensor burnout).
During the absence of the device for repairing, measures have to be taken to
ensure the safety function (for example: substitution by an equivalent device).
The HART protocol is only used for setup, calibration, and diagnostic
purposes, not during normal operation.
SIL3 application (loop powered)
The device shall claim less than 10 % of the total failure budget for a
SIL3 safety loop.
For a SIL3 application operating in Low Demand Mode the total PFD
of the SIF (Safety Instrumented Function) should be smaller than 10
the maximum allowable PFD
For a SIL3 application operating in High Demand Mode of operation the total
PFH value of the SIF should be smaller than 10
maximum allowable PFH value would then be 10
Since the circuit has a Hardware Fault Tolerance of 0 and it is a type A
component, the SFF must be > 90 % according to table 2 of IEC 61508-2 for
SIL3 (sub)system.
SIL2 application (bus powered)
The device shall claim less than 10 % of the total failure budget for a
SIL2 safety loop.
For a SIL2 application operating in Low Demand Mode the total PFD
of the SIF (Safety Instrumented Function) should be smaller than 10
the maximum allowable PFD
For a SIL2 application operating in High Demand Mode of operation the total
PFH value of the SIF should be smaller than 10
maximum allowable PFH value would then be 10
Since the circuit has a Hardware Fault Tolerance of 0 and it is a type A
component, the SFF must be > 60 % according to table 2 of IEC 61508-2 for
SIL2 (sub)system.
the manufacturer's rating and an average temperature over a long period
of time of 40 ºC. Humidity levels are assumed within manufacturer's
rating. For a higher average temperature of 60 ºC, the failure rates should
be multiplied with an experience based factor of 2.5. A similar multiplier
should be used if frequent temperature fluctuation must be assumed.
value would then be 10
avg
-7
per hour, hence the
-8
per hour.
value would then be 10
avg
-6
per hour, hence the
-7
per hour.
value
avg
-3
, hence
-4
.
value
avg
-2
, hence
-3
.
7