SAFETY MANUAL SIL K*D0-SD*-(EX)*.****(.SP), HIC2871
Planning
2.3
Safety Function and Safe State
Safety Function
The output is de-energized if the input is in low condition.
Safe State
The safety function is defined as the output is low/de-energized
(safe state: 0 V, 0 mA).
Reaction Time
The reaction time (switch off delay) for all safety functions is
< 100 ms at I
8
> 10 mA.
out