2
Actuators for modulating control AME 110 NL, AME 120 NL
Type
Power supply
running
Power consumption
standby
Frequency
Control input Y
Closing force
Stroke
Speed
Relative humidity
Max. medium temperature
Ambient temperature
Storage and transport temperature
Protection class
Grade of enclosure
Weight
- marking in accordance with
standards
* 24V AC; +10% to −15% if produced before w18y2013

Mechanical

The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting ring, which requires no tools for
mounting. The ring should be tightened by hand.
Electrical
Important: It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Auto sleep mode
1. If actuator AME 110 NL is charged by 24 V
supply voltage and if it is not installed on
AB-QM valve, it will stop in lower position and
switch off all LED indicators after 5 minutes
2. It is mandatory to drive the spindle of the
actuator to upper position before it will be
installed on AB-QM valve (please refer to
manual override drawings)!
3. Auto sleep mode switches back to learning
mode by pressing RESET button or by cycling
power supply
Each actuator is supplied with the connecting
cable for the controller.
VD.KH.C6.02 © Danfoss 01/2014
AME 110 NL
V
VA
W
Hz
V
mA
N
mm
s/mm
24
°C
III safety extra-low voltage
kg
Low Voltage Directive 2006/95/EC: EN 60730-1, EN 60730-2-14
EMC Directive 2004/108/EEC: EN 61000-6-2, EN 61000-6-3
AME 120 NL
24 AC; +20 to −15% *
2
0,5
50/60
0-10 (2-10) Ri = 110 kΩ
0-20 (4-20) Ri = 500 Ω
130
5
12
max. 80 %
120
0 ... 55
–40 ... 70
IP 42
0,3
SMT/SI