Data sheet
Manual override
(for service purposes only)
Caution:
Do not manually operate the
drive if power is connected!
Do not dismount the actuator
from the valve when it is in a
stem down position!
If dismounted in a stem down
position, there is a high risk
that the actuator gets stuck.
Dimensions (mm)
SMT/SI
Actuators for modulating control AME 110 NL, AME 120 NL
③
• Remove cover ①
• Press and hold the button ② (on the
bottom side of the actuator) during manual
override ③
• Replace cover ④
• Install actuator on valve ⑤
VD.KH.C6.02 © Danfoss 01/2014
①
Remark:
A 'click' sound after energising the actuator
indicates that the gear wheel has jumped into
normal position.
If manual override has been used, the Y
signal will not be correct until the actuator
has reached its end position. If this is not
acceptable, reset the actuator.