Base heater ON/OFF output control (option)

1)

Base heater ON conditions

When all of following conditions are met, the base heater is turned ON.
・ Outdoor air temperature (detected with Tho-A) is 3ºC or lower.
・ In the heating mode
・ When the compressor is turned ON
2)

Base heater OFF conditions

When either one of following conditions is met, the base heater is turned OFF.
・ Outdoor air temperature (detected with Tho-A) is 5ºC or higher.
・ When the compressor stop has been detected for 30 minutes continuously
・ In the cooling or dehumidifying mode
Base heater OFF
Base heater ON
3
Outdoor air temperature (ºC) [Tho-A]
5