Test Run - Mitsubishi Electric FDF71VNXVD Technical Manual

Hyper/micro inverter packaged air conditioners floor standing type
Hide thumbs Also See for FDF71VNXVD:
Table of Contents

Advertisement

Model
Power source
Power cable thickness(mm
)
MAX. over current (A) Cable length (m)
2
100VN~140VN
Single phase 3 wire
100VNX
220-240V 50Hz
5.5
220V 60Hz
125VNX,140VNX
100VS~140VS
3 phase 4 wire
3.5
380V 50Hz
100VSX~140VSX
The specifications shown in the above table are for units without heaters. For units with heaters, refer to the installation instructions or the construction
instructions of the indoor unit.
Switchgear or Circuit breaker capacity which is calculated from MAX. over current should be chosen along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a
voltage drop is 2%. For an installation falling outside of these conditions, follow the internal cabling regulations. Adapt it to the regulation in effect in each
country.

5. TEST RUN

Before conduct a test run, do not fail to make sure that the operation valves are closed.
WARNING
Turn on power 6 hours prior to a test run to energize the crank case heater.
In case of the first operation after turning on power, even if the unit does not move for 30 minutes, it is not a breakdown.
Always give a 3-minute or longer interval before you start the unit again whenever it is stopped.
Removing the service panel will expose high-voltage live parts and high-temperature parts, which are quite dangerous.
Take utmost care not to incur an electric shock or burns. Do not leave the unit with the service panel open.
When you operate switches (SW3, SW5) for on-site setting, be careful not to touch a live part.
CAUTION
You cannot check discharge pressure from the liquid operation valve charge port.
The 4-way valve (20S) is energized during a heating operation.
When power supply is cut off to reset the unit, give 3 or more minutes before you turn on power again after power is cut
off. If this procedure is not observed in turning on power again, "Communication error between outdoor and indoor unit"
may occur.
1) Test run method
(1) A test run can be initiated from an outdoor unit by using SW3-3 and SW3-4 for on-site
setting.
(2) Switching SW3-3 to ON will start the compressor.
(3) The unit will start a cooling operation, when SW3-4 is OFF, or a heating operation, when SW3-4 is ON.
(4) Do not fail to switch SW3-3 to OFF when a test run is completed.
2) Checking the state of the unit in operation
Use check joints provided on the piping before and after the four-way valve installed inside the outdoor
unit for checking discharge pressure and suction pressure.
As indicated in the table shown on the right, pressure detected at each point will vary
depending on whether a cooling or heating operation has been selected.
3) Setting SW3-1, SW3-2, on-site
(1) Defrost control switching (SW3-1)
・ When this switch is turned ON, the unit will run in the defrost mode more frequently.
・ Set this switch to ON, when installed in a region where outdoor temperature falls below zero during the season the unit is run for a heating
operation.
(2) Snow guard fan control (SW3-2)
・ When this switch is turned on, the outdoor unit fan will run for 10 seconds in every 10 minutes, when outdoor temperature falls to 3℃ or
lower and the compressor is not running.
・ When the unit is used in a very snowy country, set this switch to ON.
4) Failure diagnosis in a test run
Error indicated on the
Printed circuit board LED(The cycles of 5 seconds)
remote control unit
Red LED
Green LED
Open phase
E34
Blinking once
Blinking continuously
63H1 actuation or operation with operation valves shut
Blinking once
Blinking continuously
E40
Low pressure error or operation with operation valves shut
Blinking once
E49
Blinking continuously
If an error code other than those listed above is indicated, refer to the wiring diagram of the outdoor unit and the indoor unit.
5) The state of the electronic expansion valve.
The following table illustrates the steady states of the electronic expansion valve.
When power is turned on
During a cooling operation
Valve for a cooling operation
Complete shut position
Complete shut position
Valve for a heating operation
Full open position
6) Heed the following on the first operation after turning on the circuit breaker.
This outdoor unit may start in the standby mode (waiting for a compressor startup), which can continue up to 30 minutes, to prevent the oil
level in the compressor from lowering on the first operation after turning on the circuit breaker. If that is the case, do not suspect a unit failure.
6. UTILIZATION OF EXISTING PIPING.
Check whether an existing pipe system is reusable or not by using the following flow chart.
START
Are an outdoor unit and an indoor unit connected to the
existing pipe system to reuse?
YES
Are the existing units our products?
YES
Does the existing pipe system to reuse satisfy all of the following?
(1) The pipe length is 50m or less.
(2) The pipe size conforms to the table of pipe size restrictions.
(3) The elevation difference between the indoor and outdoor units
conforms to the following restrictions.
Where the outdoor unit is above: 30m or less
Where the outdoor unit is below: 15m or less
YES
Is the unit to install in the existing pipe system a
twin-triple-double-twin model?
NO
Is the existing pipe system to reuse free of corrosion, flaws or dents?
NO
Is the existing pipe system to reuse free of gas leaks?
(Check whether refrigerant charge was required frequently for
the system before)
NO
Are there any branch pipes with no indoor unit connected?
NO
Are heat insulation materials of the existing pipe system to
reuse free of peel-offs or deterioration?
(Heat insulation is necessary for both gas and liquid pipes)
NO
Aren't there any loose pipe supports?
Some loose pipe supports
No loose pipe supports
The existing pipe system is reusable.
<Where the existing unit can be run for a cooling operation.>
WARNING
Carry out the following steps with the excising unit (in the order of (1), (2), (3) and (4))
(1) Run the unit for 30 minutes for a cooling operation.
(2) Stop the indoor fan and run the unit for 3 minutes for a cooling operation (returning liquid)
(3) Close the liquid side operation valve of the outdoor unit and pump down (refrigerant recovery)
(4) Blow with nitrogen gas. ※ If discolored refrigeration oil or any foreign matters is discharged by the blow,
wash the pipe system or install a new pipe system.
For the flare nut, do not use the old one, but use the one supplied with the outdoor unit.
Process a flare to the dimensions specified for R410A.
Turn on-site setting switch SW5-1 to the ON position. (Where the gas pipe size is φ 19.05)
<Where the existing unit cannot be run for a cooling operation.>
Wash the pipe system or install a new pipe system.
If you choose to wash the pipe system, contact our distributor in the area.
Indoor-outdoor wire thickness × number
Grounding wire thickness
24
25
φ1.6mm x 3
26
23
φ1.6mm
15
27
SW-3-3
SW-3-4
OFF
ON
ON
- - - -
OFF
Check joint of the pipe
Cooling
Discharge pressure
operation
(High pressure)
Suction pressure
Heating
(Low pressure)
operation
Failure event
Check power cables for loose contact or disconnection
1. Check whether the operation valves are open.
(occurs mainly during a heating operation)
2. If an error has been canceled when 3 minutes have elapsed
since a compressor stop, you can restart the unit by
effecting Check Reset from the remote control unit.
(occurs mainly during a cooling operation)
When the unit comes to a normal stop
When the unit comes to an abnormal stop
During a heating operation
During a cooling operation
Full open position
Full open position
Full open position
Complete shut position
Full open position
NO
Which of the following refrigeration oils
NO
Can't
does the existing unit use?
NO
Make an inquiry
Use
Suniso, MS, Barrel Freeze, HAB, Freol,
for reusability.
YES
ether oil, ester oil
Can Use
NO
※Check with the flow chart developed for a case where
an existing pipe system is reused for a
twin-triple-double-twin model published as a
technical data sheet.
YES
Change is impossible.
Change the branching pipe to a specified type.
Change
YES
Repair is impossible.
Repair the damaged parts.
Repair
Air tightness is
impossible.
Check the pipe system for air tightness on the site.
Air tightness is OK
Remove is
impossible
Remove those branches.
Remove
Repair is impossible.
Repair the damaged parts.
Repair
Repair the damaged parts.
Repair
The existing pipe system is not reusable.
Install a new pipe system.
At the connection with the duct type indoor unit.
Model
Power source
Power cable thickness(mm
100VN,100VNX
5.5
125VN
Single phase 3 wire
140VN
220-240V 50Hz
220V 60Hz
125VNX
8
140VNX
100VS,100VSX
3 phase 4 wire
125VS,125VSX
380-415V 50Hz
3.5
380V 60Hz
140VS,140VSX
A failure to observe these instructions can result in a compressor breakdown.
Items to checkbefore a test run
Item No.used in the
Item
installation manual
Refrigerant
2
plumbing
Cooling during a test run
Heating during a test run
Normal or After the test operation
Electric
4
wiring
Charge port of the
gas operation valve
Suction pressure
(Low pressure)
Indoor unit
Discharge pressure
(High pressure)
Test run procedure
Turn
Open the gas side operation valve fully.
Open the liquid side operation valve fully.
Close the panel.
Where a remote control unit is used for unit setup on the installation site, follow instructions for unit setup on the installation site with a remote control unit.
SW3-3 ON / SW3-4 OFF: the unit will start a cooling operation.
SW3-3 ON / SW3-4 ON: the unit will start a heating operation.
When the unit starts operation, press the wind direction button provided on the remote control unit to check its operation.
Place your hand before the indoor unit's diffuser to check whether cold (warm) winds come out in a cooling (heating) operation.
Make sure that a red LED is not blinking.
Action
When you complete the test run, do not forget to turn SW3-3 to the OFF position.
Where options are used, check their operation according to the respective instruction manuals.
SWITCHES FOR ON-SITE SETTING
SW5
ON
During a heating operation
Full open position
1 2
All set to OFF for shipment
Full open position
<Table of pipe size restrictions>
◎:Standard pipe size ○:Usable
△:Restricted to shorter pipe length limits ×:Not usable
Additional charging amount of refrigerant per 1m
0.06kg/m
φ 9.52 φ 9.52 φ 12.7 φ 12.7
Liquid pipe
Pipe size
φ 15.88 φ 19.05 φ 15.88 φ 19.05
Gas pipe
◎ 
Usability 
100VN
Maximum one-way pipe length
50
100VS
Length covered without additional charge
30
◎ 
Usability 
125VN
Maximum one-way pipe length
50
125VS
Length covered without additional charge
30
◎ 
Usability 
140VN
Maximum one-way pipe length
50
140VS
Length covered without additional charge
30
<Pipe system after the branching pipe>
Additional charging amount of refrigerant per 1m
Liquid pipe
Pipe size
Gas pipe
Model
Combination type
Combination of capacity
100V
Twin
50+50
125V
Twin
60+60
Twin
71+71
140V
Triple A
50+50+50
Triple B
50+50+50
※1 Because of its insufficient pressure resistance, turn the dip switch SW5-1 provided on the outdoor unit board to the ON position for φ19.05 × t1.0.
(In the case of a twin-triple-double-twin model, this also applies to the case where φ19.05 × t1.0 is used in a pipe system after the first branching point.)
However, you need not turn the dip switch SW5-1 to the ON position, if 1/2H pipes or pipes having 1.2 or thicker walls are used.
※2 When the main pipe length exceeds 40m, a significant capacity drop may be experienced due to pressure loss in the liquid pipe system. Use φ12.7 for the
liquid main.
※3 Keep the total pipe length, not one-way pipe length, below the specified maximum pipe length.
※4 Piping size after branch should be equal or smaller than main pipe size.
※5 Piping size from first branch to indoor unit should be φ9.52 (Liquid) /φ12.7 (Gas).
When refrigerant piping is shoter than 3m, reduce refrigerant by 1kg from factory charged volume.
Any combinations of pipe sizes not listed in the table or marked with × in the table are not usable.
<The model types of existing units of which branching pipes are reusable.>
Models later than Type 8.
F D C * * *  8 □  □  □
F D C P * * *  8 □  □  □
The branching pipes used with models other than those listed above are not reusable because of their insufficient
pressure resistance. Please use our genuine branching pipes for R410A.
* * * are numbers representing horsepower. □ □ □ is an alphanumeric letter.
Formula to calculate additional charge volume
Additional charge volume (kg) = {Main pipe length (m) – Length covered without additional charge shown in the table (m)} ×
Total length of branch pipes (m)× Additional charge volume per meter of pipe shown in the table (kg/m)
※ If you obtain a negative figure as a result of calculation, no additional refrigerant needs to be charged.
Example) When an 140V (single installation) is installed in a 20m long existing pipe system (liquid φ12.7, gas φ19.05),
the quantity of refrigerant to charge additionally should be (20m-15m) x 0.08kg/m = 0.4 kg.
75
75
-
-
-
-
Indoor-outdoor wire thickness × number
)
MAX. over current (A) Cable length (m)
Grounding wire thickness
2
25
24
27
22
28
32
29
31
φ1.6mm
30
30
16
26
18
23
19
21
When you leave the outdoor unit with power supplied to it,
be sure to close the panel.
Check item
If brazed, was it brazed under a nitrogen gas flow?
Were air-tightness test and vacuum extraction surely performed?
Are heat insulation materials installed on both liquid and gas pipes?
Are operation valves surely opened for both liquid and gas systems?
Have you recorded the additional refrigerant charge volume and refrigerant pipe length on the panel's label?
Is the unit free of cabling errors such as uncompleted connection, an absent or reversed phase?
Are properly rated electrical equipments used for circuit breakers and cables?
Doesn't cabling cross-connect between units, where more than one unit are installed?
Aren't indoor-outdoor signal wires connected to remote control wires?
Do indoor-outdoor connecting cables connect between the same terminal numbers?
Are either VCT cabtyre cables or WF flat cables used for indoor-outdoor connecting cables?
Does grounding satisfy the D type grounding (type III grounding) requirements?
Is the unit grounded with a dedicated grounding wire not connected to another unit's grounding wire?
Are cables free of loose screws at their connection points?
Are cables held down with cable clamps so that no external force works onto terminal connections?
Is indoor unit installation work completed?
Where a face cover should be attached onto an indoor unit, is the face cover attached to the indoor unit?
Always carry out a test run and check the following in order as listed.
The contents of operation
SWITCHES FOR ON-SITE SETTING
ON
3
4
All set to OFF for shipment
Additional charging amount of refrigerant per 1m
0.08kg/m
0.02kg/m
φ 6.35
Liquid pipe
Pipe size
φ 15.88
Gas pipe
○※1 
△ 
△※1
Usability
100VNX
50
25
25
Maximum one-way pipe length
20
100VSX
30
15
15
Length covered without additional charge
10
○※1 
△ 
△※1
Usability
125VNX
50
25
25
Maximum one-way pipe length
20
125VSX
30
15
15
Length covered without additional charge
10
○※1 
△ 
△※1
Usability
140VNX
50
25
25
Maximum one-way pipe length
20
140VSX
30
15
15
Length covered without additional charge
10
After 1st branch
※4
After 2nd branch
0.06kg/m
0.06kg/m
φ   9.52
φ   9.52
φ   12.7
φ   15.88 φ   19.05
φ   12.7
φ   15.88
φ   19.05※1
※1
×
×
×
×
×
※5
※5
×
Additional charge volume per meter of pipe shown in the table (kg/m) +
'11 • PAC-T-160
PSB012D955F
φ1.6mm x 3
Check
Check
SW3
1 2
3
4
0.06kg/m
0.08kg/m
φ 9.52
φ 9.52
φ 12.7
φ 12.7
φ 15.88
φ 19.05
φ 15.88
φ 19.05
○※1
△※1
100
100
50
50
30
30
15
15
○※1
△※1
100
100
50
50
30
30
15
15
○※1
△※1
100
100
50
50
30
30
15
15

Advertisement

Table of Contents
loading

Table of Contents