(Ⅱ) Hyper inverter series
(1) Determination of compressor speed (frequency)
Required frequency
(a) Cooling/dehumidifying operation
Max. required
frequency
Min. required frequency
Note (1) Value in ( ) are for the models FDC125VSX, 140VSX.
(b) Heating operation
Max. required
frequency
Min. required frequency
(c) If "Silent mode start" signal is received from the remote controller, the maximum required frequency becomes same as
when the indoor air flow is set at "Lo".
(d) Max. required frequency under high outdoor air temperature in cooling mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Max. required
frequency
(e) Max. required frequency under outdoor air temperature in heating mode
Maximum required frequency is selected according to the outdoor air temperature (Tho-A).
Max. required
frequency
(f) Selection of max. required frequency by heat exchanger temperature
1)
Maximum required frequency is selected according to the outdoor unit heat exchanger temperature (Tho-R) during
cooling/dehumidifying or according to the indoor unit heat exchanger temperature (Th
2)
When there are 3 indoor unit heat exchanger temperatures (Th
Max. required
frequency
Note (1) Value in (   ) are for the models FDC125VSX, 140VSX.
(g) When any of the controls from (a) to (f) above may duplicate, whichever the smallest value among duplicated controls is
taken as the maximum required frequency.
(h) During heating, it is operated with the maximum required frequency until the indoor unit heat exchanger temperature
becomes 40°C or higher.
Model
Indoor unit air flow "P-Hi", "Hi"
Indoor unit air flow "Me", "Lo"
Model
Indoor unit air flow "P-Hi", "Hi"
Indoor unit air flow "Me", "Lo"
Model
Outdoor air temperature is
40°C or higher
Outdoor air temperature is
46°C or higher
Model
Outdoor air temperature is
18°C or higher
Outdoor air temperature is
10°C or higher
Outdoor air temperature is
5°C or higher
Model
Cooling/
Outdoor unit heat exchanger
dehumidifying
temperature is 56°C or higher
Indoor unit heat exchanger
Heating
temperature is 56°C or higher
71
100
88
75
80
50
20
20
71
100
112
100
90
60
20
20
71
100
76
75
62
70
71
100
76
75
100
100
100
-R), whichever the highest applies,
I
71
100
75
100
110
-
-
'11 • PAC-T-160
ESP-FP-1930
Unit: rps
125
140
95(92)
95(92)
60
70
20
20
Unit: rps
125
140
120
120
70
70
20
20
Unit: rps
125
140
75
75
70
70
Unit: rps
125
140
80
85
100
100
-R) during heating mode.
I
Unit: rps
125
140
95(92)
95(92)
100
100
G