FDC100,125,140VS
Outdoor unit check points
Check items with the *mark when the power is ON.
*
Power supply check:
Noise filter check:
Measure the power supply L1,L2,L3
There should be continuity.
(It is normal if it is AC380-415V)
There should be no shorts between phases.
TB
Red
L1i
L1
White
PWB3
L2
L2i
NOISE FILTER PWB
Blue
L3
L3i
Black
Ni
N
CN1 CN2-1
T12
(E)
1
2
2
3
(E1)
2
CNW2
RAM
Resistance check:
Resistance is measured
(15Ω)
1
2
L1o
52C
L2o
3
4
L3o
CT1
No
F1
5
6
3
CNW
CNIP
CNIP
CNTH
CNM
PWB1
CONTROL PWB
F1 (250V, 2A)
CNE
LED1
LED2
(Green)
(Red)
F2 (250V, 4A)
CNH
CNR
CNS
CNEEV1
SM1
SM1
SM1
LED2(Red) check:
1~5 time flash (Refer to page 121)
Capacitor check:
DC Reactor contiuity
Check for anomaly in appearance
check:55mΩ or less
such as damage,swwll,etc.
R1
R2
L1
C1
R3
R5
AC1
+4
DM
AC2
R4
C2
-6
AC3
LPT
CNPS
CNA2
CNI1
CNI3
18V
15V
2
CNA1
FMO1
CNFAN1
CNEEV2
LED1 (Yellow) Check
1 ~ 6 times flash
( Refer to page 121 )
SM2
When the outdoor
unit fan motor is
anomalous.
(Refer to page 186)
PWB2
INVERTER PWB
TB5
TB7
Red
U
TB8
DIP-IPM
White
V
TB6
W
TB9
Black
CNW2
CNR
RAM
CNE
CNI2
LED1
(Yellow)
CNW1
Fuse check:Three should
be continuity.
If it is faulty, replace the
F1 (250V, 6.3A)
CNO1
inverter board.
F2 (250V, 2.5A)
CM