Discharge Pipe Temperature Error - Mitsubishi Electric FDF71VNXVD Technical Manual

Hyper/micro inverter packaged air conditioners floor standing type
Hide thumbs Also See for FDF71VNXVD:
Table of Contents

Advertisement

Error code
E36
Remote controller:
Note (1) Value in   are for the models SRC40 ~ 60.
1. Applicable model
All models
2. Error detection method
For the error detection method,
refer to the protective control by
controlling compressor rotation
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models.
3. Condition of Error displayed
When discharge pipe
temperature anomaly is detected
2 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop.
4. Presumable cause
• Defective outdoor control
PCB
• Defective discharge pipe
temperature thermistor
• Clogged filter
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
Note:
LED
Green
Red
Keeps flashing Stays OFF
Indoor
Keeps flashing 1 5 time flash
Outdoor
5. Troubleshooting
Diagnosis
Are the
characteristics of
discharge pipe temperature
thermistor
normal?
YES
Is the
discharge pipe
temperature error persisted
during cooling
operation?
NO
Is the
discharge pipe temperature
control normal?
YES
Is the
temperature (measured
actually) at detection of
error correct?
* For the contents of control, refer to the protective control by controlling
compressor rotation speed and cooling high pressure protective control of
micro computer control function for corresponding models.
175
-
Content

Discharge pipe temperature error

* For the characteristics of discharge
pipe temperature, refer to E39.
NO
YES
NO
NO
YES
-
'11 • PAC-T-160
Countermeasure
Replace discharge pipe
temperature thermistor.
Insufficient refrigerant
amount : Recharge
refrigerant by weighing
proper amount on a scale.
Control operation check *
Defective outdoor control
PCB ➞ Replace.
Check unit side:
• Isn't filter clogged?
• Are adequate indoor,
outdoor unit installation
spaces?
• Isn't there any short-
circuit of air?
• Isn't there any fouling,
clogging on indoor heat
exchanger?