Mitsubishi Electric FDF71VNXVD Technical Manual page 167

Hyper/micro inverter packaged air conditioners floor standing type
Hide thumbs Also See for FDF71VNXVD:
Table of Contents

Advertisement

Error code
E7
Remote controller:
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor return air
temperature thermistor (Thi-A)
3. Condition of Error displayed
• When the temperature thermistor
detects -50°C or lower for
5 seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
4. Presumable cause
• Defective return air
temperature thermistor
connector
• Defective return air
temperature thermistor
• Faulty indoor control PCB
Note:
LED
Green
Red
Keeps flashing 1 time flash
Indoor
Keeps flashing Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Is the
connection of return
air temperature thermistor
connector OK?
YES
Are the
characteristics of return air
temperature thermistor
OK?
Temperature-resistance characteristic
(Broken wire)
15 
10 
(Shot circuit)
166
-
Content
Return air temperature
thermistor anomaly
NO
NO
YES
°C
5kΩ at 25
10 
20 
30 
40 
50 
Temperature (°C)
-
'11 • PAC-T-160
Countermeasure
Correct. ➞ Connect
connector.
Defective return air
temperature thermistor ➞
Replace.
Defective indoor control
PCB ➞ Replace.
(Defective return air
temperature thermistor
input circuit)

Advertisement

Table of Contents
loading

Table of Contents