Field piping
φ22.22(OD)
Heavy
4) Refrigerant pipe wall thickness and material
Select refrigerant pipes of the table shown on the right wall thickness and material as specified for each pipe
size.
This unit uses R410A. Always use 1/2H pipes having a 1.0mm or thicker wall for φ19.05 or larger pipes,
because O-type pipes do not meet the pressure resistance requirement.
Joint pipe C
φ 25.4 (ID)
φ 25.4 (ID)
Branching pipe set
Branching pipe set
(DIS-WB1,DIS-TB1)
(DIS-WB1,DIS-TB1)
Joint pipe C
φ 25.4 (ID)
Branching pipe set
(DIS-WB1,DIS-TB1)
Pipe diameter
[mm]
6.35
9.52
12.7
Minimum pipe wall thickness
[mm]
0.8
0.8
0.8
Pipe material*
O-type pipe
O-type pipe
O-type pipe
*Phosphorus deoxidized seamless copper pipe C1220T, JIS H3300
Hand
<N
Taping
2
Nitrogen
Relief valve
gas
Only use nitrogen
Brazing
gas (N
)
2
NOTE
15.88
22.22
25.4
28.58
1.0
1.0
1.0
1.0
Select pipes having a wall thickness larger
than the specified minimum pipe thickness.
O-type pipe
1/2H-type pipe
1/2H-type pipe
1/2H-type pipe