Error code
Remote controller:
E42
Outdoor control PCB
1. Applicable model
All models
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of Error displayed
• If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
• After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minute after the intial
detection. (Model FDC71 –
250 only)
4. Presumable cause
• Defective outdoor control
PCB
• Defective inverter PCB
• Faulty power supply
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
LED
Green
Indoor
Keeps flashing
Keeps flashing
Outdoor
Yellow LED or Red LED Green LED
inverter
1 time flash or 5 times flash
PCB
5. Troubleshooting
From previous page
Is the
checked result of power
transistor module
OK?
YES
• Is the space for installation of indoor and/or outdoor unit enough?
• Is there any short circuit of air on indoor and/or outdoor unit?
• At cooling, does the outdoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• Is there any liquid flooding?
Is the superheat within normal range?
Is the low pressure sensor and suction pipe temperature
thermistor normal?
• Is there any anoumalous sound on the compressor?
YES
After
resetting power for
several times does it
become normal?
YES
Temporary noise may cause of anomaly.
If noise source can be found, take countermeasure.
Red
Content
Stays OFF
1 time flash
Current cut (2/2)
Keeps flashing
Diagnosis
NO
NO
 
183
'11 • PAC-T-160
Countermeasure
• FDC71 ~ 250
Defective inverter PCB ➞
Replace.
* For model 200, 250
replace also the power
transistor module.
• FDC71 ~ 250
Defective inverter PCB ➞
Replace.
* For model 200, 250
replace also the power
transistor module.

Advertisement