Technical Data
Identity Object
This object is used to provide identification and
general information about the device. This object
is required by all DeviceNet products.
This object requires no class attributes. Its instance
attributes are the following:
Vendor
Device Type
Product Code
Revision - Major, Minor
Status
Serial Number
Product Name
Message Router
The Message Router object provides a messaging
connection point through which a Client may
address a service to any object class or instance
residing in the physical device.
This object requires no class attributes. Its instance
attributes are the following:
1. Object List - Number of Classes
General Information
Parameter 502 = "BUS".
Otherwise terminals 12 and 27 of the control card
must be connected, before motor start. In parameters
502-508 it is possible to define how to gate the control
commands from the DeviceNet with the equivalent
control commands of the digital inputs.
MG.50.H4.02 - VLT is a registered Danfoss trademark
97
2
Depends of the Drive
Depends of option
VLT 5000
®
VLT
5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Network Power Supply
The DeviceNet option is an optically isolated node,
where transceiver power is provided by the network.
External network power supply requirements are:
- 11 - 25 VDC
- 70 mA draw per VLT 5000 DeviceNet node
5
Need help?
Do you have a question about the VLT 5000 and is the answer not in the manual?
Questions and answers