Cable Lengths

Baud Rate
125k baud
250k baud
500k baud

Cable Specifications

Physical Characteristics
Two shielded pairs
Overall braid shield
Drain wire
Outside diameter
Jacket insulation *
Jacket marking *
Electrical Characteristics
DRC (braid + tape + drain)
Applicable Environmental Characteristics
Agency Certifications (U.S. and Canada)
Bend radius - installation / fixed
Operating ambient temperature
Storage temperature
Pull tension
* Other types of jacket insulation are allowable
provided that internal construction and electrical
charactersitics adhere to this specification.
6
Max. total cable length [m]
500 meters (1640 ft.)
250 meters (820 ft.)
100 meters (328 ft.)
®
VLT
5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Drop Length
Maximum
6 meters (20 ft.)
for one drop
Specification
Common axis with drain wire in center
65% coverage 36 AWG Cu braid. (individually tinned)
# 18 (19 x 30 AWG) Copper (individually tinned)
0.475 ± 0.015 inches (round),
roundness - radius delta to be within 15% of 0.5 O.D.*
0.040 inches minimum
Vendor Name & Part # 1 Pr 18 and 1 Pr 15 AWG
shielded, additional markings are acceptable
Specification
1.75 Ohms/1000 ft. (nom. @ 20°C)
Specification
NEC (UL) type, CL2/CL3 (min.)
20 x diameter / 7 x diameter
-20° to + 60°C @ 8 amps; de-rate current linearly to
zero @ 80°C
-40° to + 85°C
190 Ibs max
MG.50.H4.02 - VLT is a registered Danfoss trademark
Cumulative
156 meters (512 ft.)
78 meters (256 ft.)
39 meters (128 ft.)