Understanding Module Configuration Switches

The DeviceNet Communication module's DIP
switch settings determine:
DeviceNet node address
DeviceNet baud rate
10
®
VLT
5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
When you make changes to the switch
settings, use a pointed instrument such
as a ball point pen. DO NOT use a
pencil because damage may occur
Unpredictable operation may occur if
you fail to check connections and DIP
switch settings for compatibility with your
application. Unpredictable operation may result in
death, personal injury, and equipment damage.
Hazard of injury or equipment damage
may occur due to unintended or incorrect
machine motion. When a system
is configured for the first time, the motor must
be disconnected from the machine or process
during initial system testing.
NB!:
When setting the Communication Module's
addressing Dip Switches, you must ensure
that each serial device on the network has a
unique address. Also, all devices connected to the
network must be set at the same baud rate.
MG.50.H4.02 - VLT is a registered Danfoss trademark