Actuator controls
AC 01.2/ACExC 01.2 Profibus DP
Prm-Text-Def GSD file
(83) = "Bit: Wrn FO ring"
(84) = "Bit: WrnOnTiRunning"
(85) = "Bit: WrnOnTiStarts"
(86) = "Bit: Wrn vibration"
(87) = "Bit: Wrn dew point"
(88) = "Bit: WrnControlsTemp"
(89) = "Bit: Wrn motor temp."
(90) = "Bit: Wrn gearbox temp."
(91) = "Bit: Wrn input AIN 1"
(92) = "Bit: Wrn input AIN 2"
(93) = "Bit: WrnActProcVal"
(94) = "Bit: WrnProcSetpoint"
(95) = "Bit: WrnSetpointPos"
(96) = "Bit: Fieldbus failure"
(97) = "Bit: Local Stop"
(98) = "Bit: Wrong operation cmd"
(99) = "Bit: Channel 1 active"
(100) = "Bit: Channel 2 active"
(101) = "Bit: Motor running Close"
(102) = "Bit: Motor running Open"
(103) = "Bit: Time Sync active"
(104) = "Bit: Interlock Remote"
(105) = "Bit: Interlock Local"
(106) = "Bit: Interlock"
(107) = "Bit: Disabled"
(108) = "Bit: Config. Warning"
(109) = "Bit: Pb DataEx Ch1"
(110) = "Bit: Pb DataEx Ch2"
(111) = "Bit: Wrn FOC budget"
(112) = "Bit: FieldbusFailsafeAct.1"
(113) = "Bit: FieldbusFailsafeAct.2"
(114) = "Bit: Chan1 BusComm"
(115) = "Bit: Chan2 BusComm"
(116) = "Bit: PVST active"
(117) = "Bit: PVST fault"
Designation
(process representation)
Bit: Wrn FO cables
Bit: WrnOnTiRunning
Bit: WrnOnTiStarts
Bit: WrnOnTiRunning
Bit: WrnOnTiStarts
Bit: Wrn controls temp
Bit: Wrn motor temp
Bit: Wrn gearbox temp
Bit: Wrn input AIN 1
Bit: Wrn input AIN 2
Bit: WrnActProcVal
Bit: WrnProcSetpoint
Bit: WrnSetpointPos
Bit: Fieldbus failure
Bit: Local STOP
Bit: Wrong oper. cmd
Bit: Channel 1 active
Bit: Channel 2 active
Bit:Motor runs CLOSE
Bit:Motor runs OPEN
Bit: DP TimeSynch (Set-
Prm)
Bit: Interlock Remote
Bit: Interlock Local
Bit: Interlock
Bit: Disabled
Bit: Config. warning
Bit: Channel 1 DataEx
Bit: Channel 2 DataEx
Bit: Wrn FOC budget
Bit: Chan 1 FailState field-
bus
Bit: Chan 2 FailState field-
bus
Bit: Channel 1 activity
Bit: Channel 2 activity
Bit: PVST active
Bit: PVST error
Description
Warning:
Optical receiving signal (channel 1) incorrect (no or insuffi-
cient Rx receive level) or RS-485 format error (incorrect
bit(s))
Warning on time max. running time/h exceeded
Warning on time max. number of motor starts (starts) ex-
ceeded
Parameter not available
Parameter not available
Warning: Temperature within controls housing too high
Parameter not available
Parameter not available
Warning: Loss of signal analogue input 1
Warning: Loss of signal analogue input 2
Warning: Loss of signal actual process value
Warning: Loss of signal process setpoint
Warning: Loss of signal of actuator setpoint position
Fieldbus failure
A local STOP is active.
Push button STOP of local controls is operated.
Wrong operation command
Indicates that several operation commands were received
simultaneously via Profibus DP (e.g. Remote OPEN and
Remote CLOSE simultaneously or Remote CLOSE/Remote
OPEN and Remote SETPOINT simultaneously) or that the
max. value for a setpoint position has been exceeded (set-
point position > 1,000).
Channel 1 is the active operation command channel.
Channel 2 is the active operation command channel.
Motor runs in direction CLOSE.
Motor runs in direction OPEN.
Time synchronisation is active.
The Interlock function prevents an operation in operation
mode REMOTE.
The Interlock function prevents an operation in operation
mode LOCAL.
The Interlock function prevents an operation in operation
mode REMOTE or in operation mode LOCAL.
Operation mode disabled.
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
Channel 1 is in the data exchange state (DataEx).
Channel 2 is in the data exchange state (DataEx).
Warning: FO cable system reserve reached (critical or per-
missible Rx receive level)
No valid fieldbus communication via channel 1 (application
does not communicate with the DCS).
No valid fieldbus communication via channel 2 (application
does not communicate with the DCS).
Bus communication available on channel 1.
Bus communication available on channel 2.
Partial Valve Stroke Test (PVST) is active.
Partial Valve Stroke Test (PVST) could not be successfully
completed.
Commissioning