AUMA AUMATIC AC 01.2 Manual page 31

Profibus dp actuator controls
Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profibus DP
Bit
Designation
(process representation)
5
6
7
Table 20: Byte 25: Out of specification 1
Bit
Designation
(process representation)
0
1
2
3
4
Bit: Torque warn. CLOSE
5
Bit: Torque warn. OPEN
1)
6
Bit: SIL fault
7
Bit: No reaction
1)
The safety function indications via fieldbus are for information only and must not be used as part of a safety function. The I/O signals of
the SIL module must be used for this purpose.
Table 21: Byte 26: Out of specification 2
Bit
Designation
(process representation)
0
Bit: Wrn controls temp
1
2
3
Bit: 24 V DC, external
4
5
Bit: RTC button cell
6
Bit: RTC not set
7
Bit: Config. warning
Prm-Text-Def GSD file
Byte 25: Out of specification 1
Causes of the Out of specification signal in accordance with NAMUR recommendation
NE 107.
Prm-Text-Def GSD file
(125) = "Bit: Torque wrn
CLOSE"
(124) = "Bit: Torque wrn
OPEN"
(206) = "SIL fault"
(71) = "Bit: No reaction"
Byte 26: Out of specification 2
Prm-Text-Def GSD file
(88) = "Bit: WrnControl-
sTemp"
(68) = "Bit: 24 V DC, extern-
al"
(126) = "Bit: RTC button
cell"
(77) = "Bit: RTC not set"
(108) = "Bit: Config. Warn-
ing"
Value
Description
No signal (reserved)
No signal (reserved)
No signal (reserved)
Value
Description
No signal (reserved)
No signal (reserved)
No signal (reserved)
No signal (reserved)
1
Warning: Limit value for Torque warning CLOSE ex-
ceeded
0
No signal
1
Warning: Limit value for Torque warning OPEN exceeded
0
No signal
1
Warning: A SIL fault of the SIL sub-assembly has oc-
curred.
0
No signal
1
Warning: No actuator reaction to operation commands
within the set reaction time.
0
No signal
Value
Description
1
Warning: Temperature within controls housing too high
0
No signal
No signal (reserved)
No signal (reserved)
1
The external 24 V DC voltage supply of the controls has
exceeded the power supply limits.
0
No signal
No signal (reserved)
1
Warning: The voltage of the RTC button cell is too low.
0
No signal
1
The real time clock has not yet been set on the basis of
valid values.
0
No signal
1
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
0
No signal
Description of the data interface