The ZDUE-GPRS-PLUS-VI is compliant with the European EN60950:2006
standard, Information Technology Equipment - Safety Standards.
The ZDUE-GPRS-PLUS-VI is not designed to be connected to IT systems
for the electrical power supply.
Please read through these installation instructions carefully before using the
device.
The respective device/system is only to be set up and operated in
combination with this documentation. A device/system is only to be put into
operation and operated by qualified personnel. Qualified personnel in the
sense of the safety precautions in this documentation are persons who are
authorized to put into operation, ground and mark devices, systems and
electric circuits and systems according to the standards of safety
engineering.
Please note the following:
Warning
The device is to be used only for the intended uses indicated in the spec
sheets and in this document. The correct, safe operation of the product
assumes proper transport, proper storage, set-up and assembly as well as
careful operation and servicing.
Warning
An easily accessible, all-pole circuit breaker in the power supply circuit is
required for the house installation. Alternatively, a single-pole circuit breaker
can be used in the outer conductor as long as a distinct neutral conductor
has been integrated into the supply line. In Germany, the circuit breaker
must at least meet the requirements of the DIN VDE series 0100 standard.
Warning
The house installation requires an installation fuse that complies with the
DIN VDE series 0100 standard and is properly adapted to the cable cross-
section of the power supply line. The additional short-circuit protection must
have a selectivity of I > 1500A.
ZDUE-GPRS-PLUS-VI