Diagnostics and PlantWeb Alerts
Alerts & recommended actions
Parameter name
Internal alerts
bad_position_sensor
bad_temperature_sensor
system_temperature_exceeded
software_error
travel_deviation
shutdown_is_set
pilot valve_error
Buttonboard_error
Counter alerts
cm_life_exceeded
pm_life_exceeded
act_life_exceeded
valve_life_exceeded
Timer alerts
time_in_position_exceeded
open_travel_time_exceeded
close_travel_time_exceeded
Initialization alert
assembly error
initialization_failed
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America's: +1 281 477 4100 Europe: +36 22 53 0950 Asia/Pacific: +65 67 77 8211
Alerts
DeltaV text
Recommended actions
Bad Position Sensor Error
Feedback problem, replace control module
when possible
Bad Temperature Sensor
Temperature sensor problem, replace Control
Error
module when possible
System Temperature
Take corrective actions to bring temperature
Exceeded
within specified range.
Software Error
Software error has been detected, replace
control module when possible.
Travel Deviation
Lost position, Check air pressure
Shutdown Is Set
Internal communications problem, check
shutdown configuration for restart, Replace
Control module.
Pilot valve error
pilot valve number mismatch or pilot valve
failure has been detected
Buttonboard Error
Error is undefined, replace control module
when possible
Control Module Life Cycle
Control module life cycle exceeded, replace
Exceeded
control module
Pneumatic Module Life
Pneumatic module life cycle exceeded,
Cycle Exceeded
replace pneumatic module.
Actuator Life Cycle Ex-
Actuator life cycle exceeded, replace actuator.
ceeded
Valve Life Cycle Exceeded
Valve life cycle exceeded,valve requires
maintenance.
Time in position exceeded Time in position exceeded, take appropriate
action.
Open travel timer ex-
Open travel timer exceeded, check valve
ceeded
system.
Close travel timer ex-
Close travel timer exceeded, check valve
ceeded
system.
Assembly error
pneumatic function mismatch, check module
and actuator configuration
Initialization Failure
Device failed initialization; Check airpressure,
check actuator sizing, check valve system
FieldQ
Alert default setting
Advisory
Maintenance
n
n
y
y
n
n
y
y
n
n
y
y
n
n
y
n
y
y
n
n
n
n
n
n
n
n
y
y
n
n
y
n
n
n
y
y
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
y
y
y
y
n
n
Fail