Product data sheet
1.604.12 Rev. 3 Page 13 of 13
November 2018
Namur NE-107 Alarms
This section describes the parameter interaction to implement a
FieldQ™ QC54 Control module to the NAMUR NE-107 require-
ments as a parameter group in the Resource Block. There are
four alarm categories defined as per the NE-107 specification,
Failed, Off Specification, Maintenance, and Check function.
Maintenance Although the output signal is valid, the wear
reserve is nearly exhausted or a functions will soon be restricted
due to operational conditions e.g. build-up of deposits
Off Specification
Off-spec means that the device is operating
outside its specified range or an internal diagnostic indicates
deviations from measured or set values due to internal
problems in the device or process characteristics (e.g. bubble
formation in flow metering or valve sticking).
Check Function Output signal temporarily invalid (e.g. frozen)
due to on-going work on the device.
Failed Output signal invalid due to malfunction in the field
device or its peripherals.
Each of these categories share 32 conditions that can be defined
Parameter
Obj
Mnemonic
Type
FD_CHECK_ACTIVE
FD_CHECK_ALM
FD_CHECK_MAP
FD_CHECK_MASK
FD_CHECK_PRI
FD_EXTENDED_ACTIVE_n
FD_EXTENDED_MAP_n
FD_FAIL_ACTIVE
FD_FAIL_ALM
FD_FAIL_MAP
FD_FAIL_MASK
FD_FAIL_PRI
FD_MAINT_ACTIVE
FD_MAINT_ALM
FD_MAINT_MAP
FD_MAINT_MASK
FD_MAINT_PRI
FD_OFFSPEC_ACTIVE
FD_OFFSPEC_ALM
FD_OFFSPEC_MAP
FD_OFFSPEC_MASK
FD_OFFSPEC_PRI
FD_RECOMMEN_ACT
FD_SIMULATE
FD_VER
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America's: +1 281 477 4100 Europe: +36 22 53 0950 Asia/Pacific: +65 67 77 8211
Data Type/
Use/Model
Structure
S
Bit String
C/FD Active
R
DS-87
C/Alarm
S
Bit String
C/Contained
S
Bit String
C/Contained
S
Unsigned8
C/Alert Priority
S
Bit String
C/Contained
S
Bit String
C/Contained
S
Bit String
C/FD Active
R
DS-87
C/Alarm
S
Bit String
C/Contained
S
Bit String
C/Contained
S
Unsigned8
C/Alert Priority
S
Bit String
C/FD Active
R
DS-87
C/Alarm
S
Bit String
C/Contained
S
Bit String
C/Contained
S
Unsigned8
C/Alert Priority
S
Bit String
C/FD Active
R
DS-87
C/Alarm
S
Bit String
C/Contained
S
Bit String
C/Contained
S
Unsigned8
C/Alert Priority
S
Unsigned16
C/Contained
R
DS-89
C/FD Simulate
S
Unsigned16
C/Contained
by the device manufacturer. Each condition may be mapped or
not mapped for each category. If a condition is mapped then it
is indicated in the* ACTIVE parameter. If the condition in the *
ACTIVE parameter is not masked by the
corresponding bit in the *_MASK parameter then the condition
will be queued for broadcast using the corresponding *ALM
parameter at the associated priority indicated by *PRI
parameter. The 4 categories are defined below.
The conditions are not expected to identify explicitly the root
cause of the condition, but rather to identify it in terms of:
• Replace the device
• Replace a part of the device
• Correct a configuration problem
• Fix something outside of the device
The above list is all that the operator needs to know to restore
his process functionality and if there are more than 31 device
conditions they should be grouped by definition into these bit
Store
Size
Valid
Range
D
4
D
15
S
4
S
4
S
1
0 - 15
D
4
S
4
D
4
D
15
S
4
S
4
S
1
0 - 15
D
4
D
15
S
4
S
4
S
1
0 - 15
D
4
D
15
S
4
S
4
S
1
0 - 15
D
2
1 – manf
spec
D
9
disabled
S
2
Initial
Permission
Other
Value
Read only
ALARM
ALARM
0
ALARM
Read only
Read only
ALARM
ALARM
0
ALARM
Read only
ALARM
ALARM
0
ALARM
Read only
ALARM
ALARM
0
ALARM
0
Read only
Read only
FieldQ
Range
Check
Yes
Yes
Yes
Yes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents