Pneumatic control
Pneumatic control variations
The Control Module contains all the necessary pneumatic
components to control the actuator and control the incoming
and outgoing airflow. Pneumatically the modules are available
for three applications:
1. Spring return or
2. Double acting or
3. Double Acting - "Fail-in-Last-Position".
To achieve these functions, each Control Module can be
fitted with one or two pilot valves depending on the required
functionality:
1. One pilot valve is default and suitable for normal operation
of double acting or spring return actuators
2. Two pilot valves are required to achieve a "Fail-in-Last-
Position" functionality on double acting actuators.
Table 1:
Pilot valve specifications
Module
Voltages
QC41
24VDC (±10%)
QC42
115 VAC (±10%)
QC43
230 VAC (±10%)
Pilot valve cartridge
Pilot valve and pneumatic cartridge
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America's: +1 281 477 4100 Europe: +36 22 53 0950 Asia/Pacific: +65 67 77 8211
Power
Frequency
1W
NA
3VA
50/60Hz
3VA
50/60Hz
Pneumatic cartridge
Pilot valve
terminals
Cable range:
0.33 - 2.5mm
2
or
22-12AWG
One default pilot valve and wiring connections
Cable range:
0.33 - 2.5mm
or
2
22-12AWG
FILP = Fail in Last Position
Wiring diagram shown, is applicable for actuators with assembly code "CW". For
actuators with assembly code "CC" (reverse acting) the "Open" and "Closed"
pilot valve connections are also reversed.
Two pilot valves and wiring connections for Fail in Last Position
FieldQ
Pilot valve 1
Pilot valve 1
Pilot valve 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents