Product data sheet
1.604.13 Rev. 4 Page 9 of 9
October 2018
Wiring and Quick Connectors
AS-I Bus terminal wiring
The QC40 module can be connected to the system by hard
wiring the module to the terminals The QC40 Module can
optionally be equipped with prewired quick connectors. Two
versions are available: 7/8" or M12 (male chassis part).
Field wiring
AS-I
Power
supply
Fig 12. QC40 AS-I module wiring
Quick connector pinouts:
(male chassis part)
1
3
4
1
2
4
2
7/8" UNC
M12
Note:
Terminal 2 may be used for shield.
Fig 13. QC40 AS-I module quick connector pinouts
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America's: +1 281 477 4100 Europe: +36 22 53 0950 Asia/Pacific: +65 67 77 8211
Actuator wiring
+
1
+
1
2
-
2
3
-
3
Brown
1
1
3
2
Blue
3
3
Quick connector
Terminal
option
Connect only the brown and blue wires.
Where applicable, cut away unused wires.
Wiring for hazardous areas
Detailed safe area, Intrinsically safe or Non-Incendive/
Non-Sparking wiring instructions, will be shipped with the
product, see Installation Guide : DOC.IG.QC40.1
Quick connectors
Quick connectors, as shown are excluded for non-Incendive
or non-sparking use in hazardous area's classified as Zone 2 or
22 or Cl I, II, III, Div. 2.
Wiring dimensions
Solid wire:
2.5mm
2
Stranded wire:
0.2-3.3mm
Current
Minimum:
34 mA at 26.5V and 25°C
Maximum:
140 mA at 26.5V and 25°C
Nominal:
101 mA at 26.5V and 25°C
to 60°C
Protection:
Short circuit detection
FieldQ
max.
or 24-12 AWG
2