Emerson FieldQ Series Product Data Sheet page 43

Table of Contents

Advertisement

Product data sheet
1.604.12 Rev. 3 Page 8 of 13
November 2018
Wiring and Quick Connectors
F
™ Fieldbus terminal wiring
OUNDATION
The QC54 module can be connected to the system by hard
wiring the module to the terminals The QC54 Module can
optionally be equipped with prewired quick connectors. Two
versions are available: 7/8" or M12 (male chassis part).
Field wiring
FF
Power
supply
Quick connector pinouts:
(male chassis part)
1
3
4
1
2
4
2
7/8" UNC
M12
FieldQ
Copyright © Emerson. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website
www.emerson.com/fieldq or from your Emerson Automation Solutions - Actuation Technologies Center:
America's: +1 281 477 4100 Europe: +36 22 53 0950 Asia/Pacific: +65 67 77 8211
Actuator wiring
+
1
2
-
3
Brown
3
2
4
Green / Yellow
1
Blue
Quick connector
Terminal
Wiring for hazardous areas
Detailed safe area, Intrinsically safe or Non-Incendive/
Non-Sparking wiring instructions, will be shipped with the
product, see Installation Guide : DOC.IG.QC54.1
Quick connectors
Quick connectors, as shown are excluded for non-Incendive
or non-sparking use in hazardous area's classified as Zone 2 or
22 or Cl I, II, III, Div. 2.
Wiring dimensions
Solid wire
Stranded wire
1
2
3
: 2.5mm
max.
2
: 0.2-3.3mm
or 24-12 AWG
2
FieldQ

Hide quick links: