Chapter 12 : Maintenance - Delta Amplon RT Series User Manual

Single phase 1/1.5/2/3 kva maintenance bypass box
Hide thumbs Also See for Amplon RT Series:
Table of Contents

Advertisement

1. Unscrew the screws shown in Figure 27 to remove the cover plate of the
MANUAL BYPASS SWITCH.
NOTE :
Under the cover plate, there is a manual bypass detector (please
see Figure 28). Once the cover plate is removed, the detector will
automatically activate to send a message to the UPS. The message is to
ask the UPS to transfer into bypass mode. If there is a power interruption
while the UPS is running in bypass mode, the connected loads won't be
protected.
2. After you confirm that the UPS has been run in bypass mode, switch the
MANUAL BYPASS SWITCH to the BYPASS position (please see Figure 29).
Amplon RT Series

Chapter 12 : Maintenance

OUTPUT SOCKET
12A MAX. EACH BANK & TOTAL OUTPUT
(Figure 27)
OUTPUT SOCKET
12A MAX. EACH BANK & TOTAL OUTPUT
Manual Bypass Detector
(Figure 28)
OUTPUT SOCKET
12A MAX. EACH BANK & TOTAL OUTPUT
(Figure 29)
UPS INPUT
UPS RS-232
RS-232
NORMAL
WARNING:
OPENING THIS COVER
PLATE WILL CAUSE
BY
INVERTER SHUTDOWN.
PASS
ONLY AUTHORIZED
SERVICE PERSONNEL
CAN OPEN AND
OPERATE IT.
UPS OUTPUT
MANUAL BYPASS SWITCH
UPS RS-232
RS-232
NORMAL
BY
PASS
UPS OUTPUT
MANUAL BYPASS SWITCH
UPS RS-232
RS-232
NORMAL
BY
PASS
UPS OUTPUT
MANUAL BYPASS SWITCH
BYPASS Position
2 8
Screws
AC INPUT
UPS INPUT
AC INPUT
UPS INPUT
AC INPUT