Delta Amplon RT Series User Manual

Delta Amplon RT Series User Manual

Hide thumbs Also See for Amplon RT Series:

Advertisement

The power behind competitiveness
Delta UPS - Amplon Family
RT Series, Single Phase
5/ 6/ 10 kVA
User Manual
www.deltapowersolutions.com

Advertisement

Table of Contents
loading

Summary of Contents for Delta Amplon RT Series

  • Page 1 The power behind competitiveness Delta UPS - Amplon Family RT Series, Single Phase 5/ 6/ 10 kVA User Manual www.deltapowersolutions.com...
  • Page 2 Failure to heed these instructions and warnings will void the warranty. Copyright © 2016 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc.
  • Page 3: Table Of Contents

    Table of Contents Table of Contents Chapter 1 : Important Safety Instructions --------------------------- 1 Placement Warnings -------------------------------------------- 1 Connection Warnings ------------------------------------------- 1 Usage Warnings ------------------------------------------------- 1 Glossary of Symbols -------------------------------------------- 2 Standard Compliance ------------------------------------------ 3 Storage ------------------------------------------------------------- 4 Chapter 2 : Introduction --------------------------------------------------- 5 General Overview ----------------------------------------------- 5 Package Inspection --------------------------------------------- 5 Features ----------------------------------------------------------- 7...
  • Page 4 External Battery Connector ----------------------------------28 Parallel Port ------------------------------------------------------31 Chapter 7 : Optional Accessories -------------------------------------33 Optional Accessory List ---------------------------------------33 Optional Accessory Installation -----------------------------34 Chapter 8 : Maintenance -------------------------------------------------37 Chapter 9 : Troubleshooting --------------------------------------------38 -------------------------------40 Appendix 2 : Warranty ----------------------------------------------------42 Amplon RT Series...
  • Page 5: Chapter 1 : Important Safety Instructions

    Chapter 1 Important Safety Instructions Chapter 1 : Important Safety Instructions 1.1 Placement Warnings Install the UPS in a well ventilated area, away from excess moisture, heat, dust, Leave adequate space (at least 15cm) around all sides of the UPS for proper ventilation.
  • Page 6: Glossary Of Symbols

    1.4 Glossary of Symbols Symbol Description The UPS is in on-line mode. The UPS is in battery mode. The UPS is in bypass mode. The UPS has an internal fault. UP button DOWN button Amplon RT Series...
  • Page 7: Standard Compliance

    Chapter 1 Important Safety Instructions Symbol Description Do not connect any computer to the charger detection port. DC voltage Protective earthing conductor Bonded to ground Positive battery terminal Negative battery terminal Phase Warning Note 1.5 Standard Compliance IEC62040-1 IEC62040-2 C2 IEC61000-4-2 (ESD) Level 4 IEC61000-4-3 (Radiated Field) Level 3 IEC61000-4-4 (EFT) Level 4...
  • Page 8: Storage

    After storage and before start-up of the UPS, you must allow ° ° ° ° the UPS to adjust to room temperature (20 C~25 C or 68 F~77 F) for at least one hour to avoid moisture condensing inside the UPS. Amplon RT Series...
  • Page 9: Chapter 2 : Introduction

    Chapter 2 Introduction Chapter 2 : Introduction 2.1 General Overview This RT series UPS, available in 5kVA, 6kVA, and 10kVA, is a true on-line double- conversion UPS providing reliable and consistent sine-wave quality power to your sensitive electronic equipment. It adopts the latest technology and the highest quality components providing output power factor up to 0.9, and its efficiency in on-line mode and in economy mode can reach at maximum 92% and 96% respectively.
  • Page 10 Software CD-UPSentry 2012 1 PC Battery Cable 1 PC RS-232 Cable 1 PC Parallel Cable 1 PC Tower Stand 1 SET (4 PCS) Bracket Ear 1 SET (2 PCS) 5/ 6kVA: 8 PCS Terminal 10kVA: 6 PCS Amplon RT Series...
  • Page 11: Features

    Chapter 2 Introduction 2.3 Features True on-line design UPS protects your sensitive electronic equipment from pow- er interruption. Wide AC input voltage range (100Vac~300Vac) reduces frequent transfer from on-line mode to battery mode to save battery consumption and prolong battery life.
  • Page 12 Enables set up of “1+1” parallel redundant system (with optional manual bypass box) to increase the system availability and reliability. The fan(s) automatically adjusts the fan speed to prolong fan life. Amplon RT Series...
  • Page 13: Chapter 3 : Front Panel And Rear Panel

    Chapter 3 Front Panel and Rear Panel Chapter 3 : Front Panel and Rear Panel 3.1 Front Panel (Figure 3-1 : Front Panel) Item Description On-line LED Indicates that the UPS is in on-line mode. Battery LED Indicates that the UPS is currently in battery mode and the external battery is discharging now.
  • Page 14: Rear Panel

    SMART SLOT RS-232 INPUT BREAKER 230Vac 63A Nader 230/400V- UPS OUTPUT AC INPUT 240Vdc 42.6A EXTERNAL BATT. CONNECTOR EXTERNAL MINI SLOT BATTREY CONNECTOR CAUTION: DO NOT DISCONNECT BATTERY CABLE UNDER LOAD. (Figure 3-3 : 10kVA Rear Panel) Amplon RT Series...
  • Page 15 Chapter 3 Front Panel and Rear Panel Item Description Protects the utility power from further damage when the Input Breaker UPS fails. AC Input Connects the UPS to the mains. Terminal Block UPS Output Connects to the load. Terminal Block Cools and ventilates the UPS.
  • Page 16: Chapter 4 : Installation

    : Fix the rail on the rack. Step : Insert the UPS in the rack and tighten the screws. If you want to use a non-Delta rail kit, please only follow Step (Figure 4-1 : UPS Bracket Ear Installation) (Figure 4-2 : Rcak Mounting)
  • Page 17: Tower Mounting

    Pull out the UPS control panel and rotate it 90° clockwise . See Figure 4-4 . Carefully lift the UPS upright with the Delta logo shown on the control panel facing up. See Figure 4-5. Place the UPS inside the tower stands .
  • Page 18 (Figure 4-6 : Place the UPS Inside the Tower Stands) Leave adequate space (at least 15cm) around all sides of the UPS for good ventilation. NOTE : A minimum of two people are required to execute action and action Amplon RT Series...
  • Page 19: Connection

    Chapter 4 Installation 4.3 Connection UPS Connection Warnings 1. When connecting the UPS to the mains and the load, it is highly recommended that you install the protective devices. The protective devices must use and diagram below. UPS Power Suggested Suggested Supplier Rating Protective Device...
  • Page 20 2) Calculate the power consumption of the load to ensure that an overload condition will not occur. 3) Ensure that the screws are tightly fixed after the connection. The tightening torque should be 18±2Kgf.cm. Amplon RT Series...
  • Page 21 Chapter 4 Installation 4. After the UPS is connected to the utility power, the following sequence of events will occur. 1) The fan(s) in the rear panel comes on. ONLINE UPS 3) After above message appears, the LCD will show the UPS is in ‘BYPASS MODE’, and the bypass LED will illuminate (yellow).
  • Page 22: Chapter 5 : Operation

    INVERTER OK INVERTER OK. NOTE : When the LCD shows each screen ( ) , the bypass LED will illuminate (yellow). Now, the UPS is in on-line mode and the on-line ONLINE MODE 00.00KW / 000% illuminates (green). Amplon RT Series...
  • Page 23 Chapter 5 Operation UPS Start-up with Battery Press the ‘ON’ button for 3~5 seconds to start up the UPS. 1. When you press the ‘ON’ button, the LCD will show the message below. ONLINE UPS 2. After the ‘ON’ button is pressed for 3~5 seconds, the system will beep. Release the button and the UPS will start up.
  • Page 24: Ups Turn-Off

    INPUT VOLTAGE 000V / 00.0Hz In different operation modes, the LCD will display different information. BYPASS VOLTAGE 000V / 00.0Hz OUTPUT VOLTAGE 000V / 00.0Hz BATTERY CAPACITY 000V / 000% REMAINING TIME 0000 MINUTES ON-LINE 5kVA V00 CV00 Amplon RT Series...
  • Page 25 Chapter 5 Operation NOTE : 1. Please use the UP “ ” and DOWN “ ” buttons on the front control panel to switch back and forth between screens. The UPS supports multi-language LCD display. If you need to change the default language setting, please contact your local dealer or customer service.
  • Page 26: Firmware Version Look-Up

    If not, the UPS won’t turn on and the alarm mes- sage below appears. UPS1 / UPS2 FW VER NOT COMPATIBLE If the message above appears, please contact your local dealer to upgrade the Amplon RT Series...
  • Page 27: Operation Modes

    Chapter 5 Operation 5.5 Operation Modes Online Mode During on-line mode, the on-line LED illuminates (green). The critical load is supplied by the inverter, which derives its power from the utility AC power, and the UPS charges the batteries as needed and provides power protection to the equipment.
  • Page 28 50Hz or 60Hz. After the output frequency is set up, the system will automatically disable the bypass function. Please note that once the inverter shuts down, there is no bypass output. During converter mode, the on-line LED illuminates (green). Amplon RT Series...
  • Page 29: Chapter 6 : Communication Interfaces

    Chapter 6 Communication Interfaces Chapter 6 : Communication Interfaces NOTE : The UPS can still function properly without making the connections below. 6.1 RS-232 Port RS-232 port (9-pin female connector) is built into the UPS rear panel. You can use the provided RS-232 cable to connect the UPS with a computer and use the included CD to install the UPSentry 2012 software to check and monitor the UPS status via a computer.
  • Page 30: Repo Port

    This REPO port can also be used for the ROO application, which lets you remotely turn on/ off the inverter. If you need detailed ROO information or ROO setup service, please contact your local dealer or customer service. cian. Amplon RT Series...
  • Page 31: Smart Slot

    Chapter 6 Communication Interfaces 6.3 SMART Slot Install an SNMP card in this SMART slot to remotely control and monitor the UPS status via a network. You can also insert the Relay I/O or ModBus card in this slot to let the UPS have dry contact and ModBus communication functions respectively. Please see Figure 6-2 &...
  • Page 32: External Battery Connector

    This connector is for connection to an external battery pack. Please see below for relevant information. Battery Charge Charge Low Battery The Number Voltage Current Shutdown Of Batteries 0.7A 5kVA/ 6kVA 217.6Vdc 168V±3% 12V x 16 PCS (default) Amplon RT Series...
  • Page 33 Please refer to the Quick Guide, User Manual or Installation & Operation Guide included in the package of the external battery pack. 3. Non-Delta external battery pack: When connecting a non-Delta external battery pack with the UPS, please the actual discharge current to decide the breaker’s current capacity.
  • Page 34 2. A battery can present a risk of electric shock and high short-circuit current. 3. Servicing of batteries and battery packs must be performed or battery packs and the required precautions. Keep unauthorized personnel away from batteries and battery packs. Amplon RT Series...
  • Page 35: Parallel Port

    Chapter 6 Communication Interfaces 6.6 Parallel Port This is for UPS parallel communication. Only two UPS units with the same capacity, voltage and frequency can be coupled via the provided parallel cable to run in parallel mode. The total load will be shared equally by the two units. If one of the two parallel units fails: 1.
  • Page 36 External Battery Packs Battery Packs Parallel Box SMART SLOT SMART SLOT CHARGER CHARGER REPO PARALLEL REPO PARALLEL DETECTION DETECTION (Figure 6-7) NOTE : If you need UPS parallel service, please contact your local dealer or customer service. Amplon RT Series...
  • Page 37: Chapter 7 : Optional Accessories

    Dust Filter sure UPS reliability and to prolong product life. Rail Kit Provides external batteries to let the UPS con- Delta External Battery tinue supplying power to its connected loads Pack when a power outage occurs. Monitors temperature, humidity and other condi- tions in a room environment.
  • Page 38: Optional Accessory Installation

    Loosen the top cover’s screws to remove the top cover (Figure 7-1 ModBus card (Figure 7-1 Insert the Mini SNMP/ Mini Relay I/O/ Mini USB/ Mini ModBus card into the slot and tighten the screws (Figure 7-1 Amplon RT Series...
  • Page 39 Chapter 7 Optional Accessories Figure 7-1 Replace the top cover and tighten the screws (Figure 7-1 Mini SNMP Card Mini ModBus Card Mini Relay Card Mini USB Card Mini Relay Mini USB Mini ModBus Card Card Card (Figure 7-1) 2. For 10kVA UPS: Remove the MINI slot's cover from the rear panel (Figure 7-2 Loosen the top cover’s screws to remove the top cover (Figure 7-2 ModBus card (Figure 7-2...
  • Page 40 Remove the MINI slot's cover from the rear panel (Figure 7-4 Insert the Mini TVSS card into the slot and tighten the screws (Figure 7-4 Mini TVSS Card (Figure 7-4) NOTE : Please contact your local dealer for more information about the optional cards. Amplon RT Series...
  • Page 41: Chapter 8 : Maintenance

    Chapter 8 Maintenance Chapter 8 : Maintenance 1. UPS Cleaning: Regularly clean the UPS, especially the slits and openings, to ensure that air-gun to clean the slits and openings to prevent any object from blocking or covering these areas. 2. UPS Regular Inspection: Regularly check the UPS every half year and inspect: 1) Whether the UPS, LED, or alarm function has any abnormality.
  • Page 42: Chapter 9 : Troubleshooting

    2. Output SCR has short issue. 1. Bypass SCR has no driver signal. BYPASS SCR Contact service personnel. FAIL 2. Bypass SCR has short issue. signal. RECTIFIER FAIL Contact service personnel. INVERTER FAIL Inverter is damaged. Contact service personnel. Amplon RT Series...
  • Page 43 Chapter 9 Troubleshooting Problem Possible Cause Solution I/P FUSE Input fuse is broken. Contact service personnel. BROKEN O/P FUSE Output fuse is broken. Contact service personnel. BROKEN FAN FAIL Fan(s) is damaged or stuck. Contact service personnel. Remove the unnecessary OVERLOAD UPS is overloaded.
  • Page 44 111 ~ 125%: 5 minutes; Capability 126 ~ 150%: 30 minutes The Overload Release (Rating Load) Output Output Frequency 50/60 Hz ± 0.05 Hz (Battery Mode) Crest Factor (CF) Online Mode: 92% (full load) Resistance Load) ECO Mode: 96% (full load) Amplon RT Series...
  • Page 45 Appendix 1 Model RT5K RT6K RT10K Type Sealed Lead-Acid Battery 12V x 20 PCS Battery & Number of 12V x 16 PCS Charger Battery 12V x Charge Current 4A (maximum) Audible Noise 54 dBA * Dimensions- W x D x H 440.0 x 623.0 440.0 x 670.5 x 88.5 mm (I/P &...
  • Page 46: Appendix 2 : Warranty

    The individual user should take care to determine prior to use whether the environment and the load characteristic are suitable, adequate or safe for the installation and the usage of this product. The User Manual must be carefully followed. Seller makes no representation or warranty as to the Amplon RT Series...
  • Page 48 5012313302...